Reference guidelines, General characteristics, Accessories see enclosed packing list – HT instruments PQA820 User Manual

Page 22

Advertising
background image

PQA820

EN – 21

AC Power/Energy – (Vmeas > 200V, Pf=1)

Clamp FS [A]

Range [W] [Wh]

Resolution [W] [Wh]

Accuracy

1< FS

 10

0.000k

 9.999k

0.001k

(0.7rdg + 3W/Wh)

10.00k

 99.99k

0.01k

(0.7rdg+30W/Wh)

10< FS

 200

0.00k

 99.99k

0.01k

(0.7rdg+30W/Wh)

100.0k

 999.9k

0.1k

(0.7rdg+300W/Wh)

200< FS

 1000

0.0k

 999.9k

0.1k

(0.7rdg+0.3kW/kWh)

1000k

 9999k

1k

(0.7rdg+3kW/kWh)

Vmeas = Voltage in which the power is measured

Power factor and Cos

Range

Resolution (°)

Accuracy (°)

0.20

 0.50

0.01

0.6

0.50

 0.80

0.7

0.80

 1.00

1.0

Voltage and current harmonics

Range

Resolution

Accuracy

DC

 25

th

0.1V / 0.1A

(5.0rdg + 2dgt)

26

th

 33

th

(10rdg + 2dgt)

34

th

 49

th

(15rdg + 2dgt)

The harmonics will be zeroed under the following conditions

DC: if the value of DC <0.5% of the value of the fundamental or if the DC value < 0.5% of the clamp's full scale

1st harmonic: if the value of the 1st harmonic <0.5% of the clamp's full scale

 2nd

 49th harmonic: if the value of harmonic <0.5% of the value of the fundamental or if <0.5% of the FS clamp

11.2. REFERENCE GUIDELINES

Safety: IEC/EN

61010-1

+

A2(1996)

Insulation: double

insulation

Pollution level:

2

Max. height of use:

2000m (6562ft)

Measurement category:

CAT IV 300V AC (to ground), Max 460V between inputs

11.3. GENERAL CHARACTERISTICS

Mechanical characteristics:
Dimensions (L x W x H):

245 x 210 x 110mm (10 x 8 x 4in)

Weight: 1.5kg

(3lv)

Power supply
Internal power supply:

rechargeable Li-ION battery

Battery life:

approx. 1 hour

External power supply:

Ing. Red-Yellow: 100

 415V, 50/60Hz, 20mA

Measurement and memory
Number of samples per period:

128, (64 in “Real Time” connection)

Max. recordable parameters:

383 (simultaneously)

Max. recordable voltage anomalies:

65530

Integration period:

5, 10, 30s, 1, 2, 5, 10, 15, 60min

Recording autonomy:

> 30 days (@ IP = 10 minutes)

Memory: 8Mbyte

11.4. ENVIRONMENT
11.4.1. Environmental conditions for use

Reference temperature:

23°C ± 5°C (73°F ± 41°F)

Operating temperature:

0°C ÷ 40 °C (32°F ÷ 104°F)

Allowable relative humidity:

<80%HR

Storage temperature:

-10°C ÷ 60°C (14°F ÷ 140°F)

Storage humidity:

<80%HR

This instrument satisfies the requirements of Low Voltage Directive 2006/95/EEC (LVD) and of EMC

Directive 2004/108/EEC

11.5. ACCESSORIES
See enclosed packing list