4. NOMENCLATURE

4.1. INSTRUMENT

DESCRIPTION

CAPTION:
1. Indication LEDs
2. Description of the indication LEDs
3. USB port
4. Voltage and Current inputs
5. Keyboard


Fig. 1: Instrument description

4.2. KEYBOARD

DESCRIPTION

The keyboard includes the following keys:
ON/OFF: pressing this key to switches the instrument on. Press the key approx. 2s to

switches the instrument off. If the instrument do not switch off press and hold this key
for at least 5s

START/STOP: for manually starting and stopping recording (see § 7 and 7.3).
SYSTEM: It allows for the selection of the electrical system (Single phase, Three phase 3-

wire and 4-wire)

WiFi/RF: it allows for the selection of the communication mode, WiFi or RF (only for the

communication with other HT instruments).

4.3. DESCRIPTION OF THE LED
LED Description

POWER

It describes the status and supply mode of the instrument:
Off:

instrument switched off

Flashing green:

instrument switched on supplied by internal batteries

Flashing red:

internal batteries almost flat

STATUS

It described the instrument status:

Off:

No recording in progress

Flashing green:

Recording in progress

Green:

Instrument waiting to start recording. Recording will always start at

the beginning of the minute after the START button has been pressed
/ receipt of the start recording control

Flashing red: Memory

full

Red:

Internal error – use the management software to identify the type of

malfunction. Some of them may also prevent recording.

RF/WiFi

It described what communication mode is currently set in the instrument:
Off: WiFi

mode

Flashing green:

RF mode (only for connection with other HT instruments)

CONNECTION It indicates if a WiFi or RF connection is active (according to the communication mode set)

SYSTEM

It indicates the electrical system currently set:

Off: Single-phase

mode

Flashing green:

Three-phase without neutral mode

Green:

Three-phase with neutral mode

ERROR

It indicates possible connection errors:
Off:

No error detected

Flashing red:

Phase sequence incorrect

Red:

One of the active powers measured by the instrument is negative.

Table 1: Description of LEDs