HT instruments М75 User Manual

Page 38

Advertising
background image

M72 - M73 - M74 - M75

EN - 36

4. If during measurement an excessive

contact voltage is detected (higher than
50V) the instrument does not perform the
test and emits a prolonged sound to
signal the anomalous situation. The
screen beside is displayed for 5 seconds
after which the instrument displays the
default screen of Ra test

5. The instrument dispalys the

symbol

when:

The instrument is operating in a

critical situation as for example in
presence of overvoltages

The instrument cannot guarantee the

measuring uncertainty lower than
30% of the reading, according to
IEC/EN61557-1


6. If during measurement the green probe is

connected to the phase conductor and
the black probe is connected to the
protective conductor, the instrument does
not perform the test and emits a
prolonged sound to signal the anomalous
situation. The screen beside is displayed
for 5 seconds after which the instrument
displays the default screen of Ra test.
This can happen even if the wrong
connection is performed on the back side
of the power socket