ELECTRICAL CONNECTIONS

3

53

IFC 300

www.krohne.com

08/2010 - 4000070303 - QS IFC 300 R06 en

100...230 VAC (tolerance range: -15% / +10%)

100...230 VAC (tolerance range: -15% / +10%)

100...230 VAC (tolerance range: -15% / +10%)

100...230 VAC (tolerance range: -15% / +10%)

• Note the power supply voltage and frequency (50...60 Hz) on the nameplate.
• The protective ground terminal PE

PE

PE

PE of the power supply must be connected to the separate U-

clamp terminal in the terminal compartment of the signal converter
For 19" rack-mounted housing please refer to the connection diagrams.

12...24 VDC (tolerance range: -55% / +30%)

12...24 VDC (tolerance range: -55% / +30%)

12...24 VDC (tolerance range: -55% / +30%)

12...24 VDC (tolerance range: -55% / +30%)

• Note the data on the nameplate!
• When connecting to functional extra-low voltages, provide a facility for protective separation

(PELV) (acc. to VDE 0100 / VDE 0106 and/or IEC 364 / IEC 536 or relevant national
regulations).

24 VAC/DC (tolerance range: AC: -15% / +10%; DC: -25% / +30%)

24 VAC/DC (tolerance range: AC: -15% / +10%; DC: -25% / +30%)

24 VAC/DC (tolerance range: AC: -15% / +10%; DC: -25% / +30%)

24 VAC/DC (tolerance range: AC: -15% / +10%; DC: -25% / +30%)

• AC: Note the power supply voltage and frequency (50...60 Hz) on the nameplate.
• DC: When connecting to functional extra-low voltages, provide a facility for protective

separation (PELV) (acc. to VDE 0100 / VDE 0106 and/or IEC 364 / IEC 536 or relevant national
regulations).

INFORMATION!
240 VAC + 5% is included in the tolerance range.

INFORMATION!
12 VDC - 10% is included in the tolerance range.

INFORMATION!
12 V is not

not

not

not included in the tolerance range.