ELECTRICAL CONNECTIONS

4

27

UFM 530 HT

www.krohne.com

12/2013 - 4002393201- HB UFM 530 HT R02 en

The following Ex-i Modis versions have two Modis modules, providing intrinsically safe input /
output circuits. Modis versions don't have analogue inputs A1 / A2.

Ex-i (Modis) version

Figure 4-9: Terminals for instrument with Ex-i (Modis)

Terminal

Function

Specification

1

Neutral mains power supply

100...240 VAC, 24 VAC or 24 VDC

2

Live mains power supply

100...240 VAC, 24 VAC or 24 VDC

3

Ground for pulse, frequency or status
output

4

Pulse, frequency or status output

I

max

= 150 mA, U

max

= 32 VDC / 24 VAC,

maximal frequency = 2 kHz.

5

Current output

Current output (I): I ≤ 22 mA,
R

load

≤ 680 Ω, U

max

= 15 VDC.

6

Ground for current output

Advertising