Measurement status

Level measurement lost

E

1

The device can no longer find

the product surface. The

measurement is held at the

last measured value.

Check the tank contents

using another method of

measurement. If the tank is

empty (the level is below the

end of the probe), then fill the

tank until product level is in

the measurement range. If

the tank is full (the level is in

the blocking distance), then

remove the contents from the

tank until the level is back in

the measuring range. If the

product was lost and the tank

is neither full nor empty,

contact your supplier.

When the level return signal

and the probe end return

signal are lost. This is

applicable to automatic

(Direct/TBF) measurement

mode only.

If the device is in direct mode,

adjust the Level Threshold

(menu item C.1.16). If the

device is in TBF mode, adjust

the Probe End Threshold

(menu item C.1.18). For more

data, refer to

Thresholds and

parasitic signals

on page 92.

Level measurement low

W

The product is in the empty

area. The measurement is

held at the sensor length.

Fill the tank to at least the

bottom of the measuring

range to continue

measurement.

The product is outside the

measuring range. The

measurement is incorrect or

held at the last measured

value by the device.

Measurement old

E

This error can occur if the

power supply is not sufficient

to operate the device

correctly for 1 minute. After 1

minute the error message

"Measurement old" is

recorded. You can change this

time in supervisor mode. Go

to Advanced Setup > Output

Advanced Setup > Output

Advanced Setup > Output

Advanced Setup > Output

1 > Error Handling Delay

1 > Error Handling Delay

1 > Error Handling Delay

1 > Error Handling Delay

(5...300 seconds).

Make sure that the power

supply for output 1 has a

min./max. value of

14...30 VDC (20...36 VDC for

Ex d-approved devices) when

current output is at 22 mA.

Interface measurement lost

2

W

1

The device can no longer find

the interface.

Check the tank contents

using another procedure. If

the interface is too low (the

interface is below the end of

the probe), then fill the tank

with interface product until it

is in the measurement range.

If the interface too high (the

interface is in blocking

distance), then remove the

contents from tank until the

interface is back in the

measuring range. If it is none

of these two, then there is

possibly an emulsion at the

interface. Wait for the device

to find the interface again.

Error Message

Error

code

Description

Corrective action