Operation, 5 distance measurement – KROHNE OPTIFLEX 2200 C_F EN User Manual

Page 84

Advertising
background image

6

OPERATION

84

OPTIFLEX 2200 C/F

www.krohne.com

07/2013 - 4000668002 - HB OPTIFLEX 2200 R02 en

How to change from multidrop to point-to-point mode

• Enter the supervisor menu.
• Push [>>>>], 5 × [







] and [>>>>] to go to menu item ADDRESS (2.6.1).

• Push [>>>>] to change the value. Enter the value 0 and push [^

^

^

^] to confirm.

• Push [^

^

^

^] to go back to the "STORE" screen.

• Push [







] or [







] to set the screen to STORE YES

STORE YES

STORE YES

STORE YES and push [^

^

^

^].

i

The output is set to point-to-point mode. The current output changes to a range of 4...20 mA
or 3.8...20.5 mA (this range is set in menu item RANGE I (2.4.2)).

6.4.5 Distance measurement

The device current output agrees with the distance measurement when the output is
set to "Distance". Menu items used for distance measurement are:

• Output Function (2.4.1 OUTPUT)
• Tank Height (2.3.1 TANK HEIGHT)
• Blocking Distance (2.3.4 BLOC. DIST.)

Use the flange facing or thread stop as the reference point for the 4 and 20 mA current output
settings. The 4 and 20 mA current output settings are the minimum and maximum points of the
measurement scale.

For more data about the menu items, refer to

Function description

on page 74.

Figure 6-4: Distance measurement

1 Tank Height (2.3.1 TANK HEIGHT)
2 Blocking Distance (2.3.4 BLOC. DIST.)
3 4 mA Setting (2.4.3 SCALE 4mA)
4 20 mA Setting (2.4.4 SCALE 20mA)
5 Maximum effective measuring range
6 Non-measurement zone