General safety information, 1 scope of the document, 2 device description – KROHNE OPTIWAVE 6300C ATEX EN User Manual

Page 4: 3 standards and approvals

Advertising
background image

1

GENERAL SAFETY INFORMATION

4

OPTIWAVE 6300 C

www.krohne.com

06/2010 - 4000482302 - AD ATEX OPTIWAVE 6300 R02 en

1.1 Scope of the document

These instructions are applicable only to the explosion-protection version of the radar level
transmitter. For all other data, use the Quick Start and Handbook. If you do not have these
documents, please contact the nearest office or download them from the manufacturer's
internet site.

1.2 Device description

This device is a 2-wire level transmitter that uses FMCW (Frequency-Modulated Continuous
Wave) radar technology. It measures level, volume, distance to surface, and reflectivity of solid
particles, granulates and powders.It is suitable for installation on storage tanks and silos.
Measurements are displayed via a DTM (device type manager) for remote communication or on
an optional integrated display screen with wizard-driven setup and online help functions.

The level transmitter is approved for use in potentially explosive atmospheres when equipped
with the appropriate options.

1.3 Standards and approvals

The certificate is given on the CD-ROM supplied with the device. You can also download the
certificate from our internet site.

INFORMATION!
The information in these supplementary instructions only contains the data applicable to
explosion protection. The technical data for the non-Ex version in the Handbook shall be valid in
its current version, provided that it is not rendered invalid or replaced by these supplementary
instructions.

WARNING!
Installation, commissioning and maintenance may only be carried out by "Personnel trained in
explosion protection".

DANGER!
In compliance with European Directive 94/9/EC (ATEX 100a), the ATEX version of the device
described in these Supplementary Instructions conforms to European Standards EN 60079-
0:2006, EN 60079-1:2007, EN 60079-11:2007, EN 60079-26:2007, EN 60079-27:2008, EN 61241-
0:2006, EN 61241-1:2004 and EN 61241-11:2006. The Ex ia / Ex iaD and Ex d[ia] / Ex tD[iaD]
versions are certified for use in hazardous areas by the KEMA Quality B.V. under
KEMA 04ATEX1218 X.

WARNING!
Carefully read the ATEX approval certificate. Obey the boundary conditions.