Installation, 2 operating conditions, 1 ambient and flange temperature – KROHNE OPTIWAVE 7300 IECEx User Manual

Page 9

Advertising
background image

INSTALLATION

2

9

OPTIWAVE 7300 C

www.krohne.com

10/2010 - 4000176502 - AD IECEX OPTIWAVE7300 R02 en

Connection and operation of the purging connection are the responsibility of the user. The
operator is also responsible for selection of a suitable fluid to purge the device.

• If the screw is removed, make sure that the installation agrees with the Ex requirements for

the purging system.

2.2 Operating conditions

The allowable ambient temperature and corresponding flange temperature range for the device
depends on the Ex equipment category and temperature classes marked on the nameplate.

2.2.1 Ambient and flange temperature

The equipment protection level (EPL) and temperature class give the ambient temperature and
related flange temperature ranges for the device.

EPL Ga: Ex ia devices only - with the 4...20 mA output option

EPL Ga/Gb: Ex ia and Ex d[ia] devices - with the 4...20 mA output option

WARNING!
The gasket temperature must be in the approved limits. For more data, refer to "Pressure and
temperature ranges" in the Installation chapter of the handbook.

Temperature

class

Ambient temperature

Flange temperature

[°C]

[°F]

[°C]

[°F]

T6

-20…+57

-4…+122

-20…+60

-4…+140

Temperature

class

Ambient temperature

Flange temperature

[°C]

[°F]

[°C]

[°F]

T6

-40…+57

-40…+134

-20…+60

-4…+140

T5

-40…+72

-40…+161

-20…+60

-4…+140

T4

-40…+80

-40…+176

-20…+60

-4…+140