KYORITSU 3132A User Manual

Page 4

Advertising
background image

CAUTION

Always make sure to set the range switch to the appropriate position

before making measurements.

Do not expose the instrument to the direct sun, dew fall or extreme

temperature and humidity.

When the instrument will not be in use for a long period of time, place it

in storage after removing batteries.

Use a damp cloth soaked in water or neutral detergent for cleaning the

instrument. Do not use abrasives or solvents.

― 3 ―

DANGER is reserved for conditions and actions that are likely to cause

serious or fatal injury.

WARNING is reserved for conditions and actions that can cause

serious or fatal injury.

CAUTION is reserved for conditions and actions that can cause minor

injury or instrument damage.

DANGER

Do not use this instrument on energized (LIVE) circuits.

Do not make measurement in the presence of flammable gasses.

Otherwise, the use of the instrument may cause sparkling, which leads

to an explosion.

Always keep your fingers behind the barrier on test probe during

measurement.

Never use the instrument if its surface or your hand is wet.

Never open the battery compartment cover while making measurement.

WARNING

Do not attempt to take any measurements, if any abnormal conditions

are noted, such as broken test probe and cracked enclosure of the

instrument.

Never change ranges with test probe connected to the equipment under

test.

Do not install substitute parts or perform any unauthorized modification

of the instrument. Return the instrument to Kyoritsu or your distributor

for service and repair to ensure the safety features are maintained.

Do not replace batteries when the surface of the instrument is wet.

Make sure to disconnect the test probe from the instrument before

opening the battery compartment cover for battery replacement.

― 2 ―

3132A-E/03-08 03.8.6 10:33 AM ページ 2