KYORITSU 4120A User Manual

Page 16

Advertising
background image

― 14 ―

For instance in a TN system with nominal mains voltage Uo = 230 V
protected by gG fuses the Ia and max Zs values could be:

Using the current ranges on models 4120A and 4118A can be also tested
the Prospective Fault current.
Prospective Fault current measured by instruments must be higher than Ia
of the protective device concerned

Practical example of verification of the protection in a TN system according
to the international Standard IEC 60364.

Fig.9

Rating

(A)

Disconnecting time 5s

Ia (A)

Zs (Ω)

Ia (A)

Zs (Ω)

Disconnecting time 0.4s

6

10
16
20
25
32
40
50
63
80

100

28
46
65
85

110
150
190
250
320
425
580

8.2

5

3.6
2.7
2.1

1.53
1.21
0.92
0.71
0.54
0.39

47
82

110
147
183
275
320
470
550
840

1020

4.9
2.8
2.1

1.56
1.25
0.83
0.72
0.49
0.42
0.27
0.22

L1
L2
L3
N
PE

R

O

Fuse gG 16A