KYORITSU 4120A User Manual

Page 18

Advertising
background image

― 16 ―

6.3 Measurement of Line Impedance and Prospective Short Circuit Current
Line Impedance on single-phase system is the impedance measured
between phase and neutral terminals.
Measurement principle used inside the instrument is exactly the same as at
Fault Loop Impedance measurement, but the measurement is carried out
between L and N terminals.

Breaking current capacity of installed over-current protection devices should
be higher than Prospective Short-Circuit current, otherwise it is necessary to
change the rated current of involved over-current protection device.

Practical example of line impedance test and prospective short-circuit
current test (only for models 4120A and 4118A):

The figure below shows in marked line the Line impedance phase to neutral
for TN system.

Fig.11

WARNING

(OLD-TT system only)

DO NOT PRESS the "Test button" if the display reads a value of

220V!
The RCD could trip during the tests also with model 4120A.

CAUTION

● The D-LOK circuit of 4120A can not works with 127V between

phase to earth.

L1
L2
L3
N
PE

R

O

RCD

L

PE

N

Advertising
This manual is related to the following products: