6.4 Phase rotation test


L LED

and R LED for Phase rotation test may

operate on various wiring systems, but effective
testing result can be obtained only on Three-phase
4-wire system.

►Grasp the instrument firmly and connect both

probes to the object under test.

►Phase-to-phase voltage is indicated by each

Voltage LED.

R LED lights up for Right rotary field.















Grasp Firmly!!!



L LED lights up for Left rotary field.













Grasp Firmly!!!




The principle of measurement
The instrument detects the phase rising order
regarding the user as EARTH.

NOTE

Function of this test may not be fully achieved if
the insulation condition of user or of the equipment
under test is not enough.

6.5 Continuity test

WARNING

Make sure the object under test isn’t live.


Instrument operates as follows when measuring
Continuity.

►All LEDs other than Power LED should be
flashing, and buzzer should sound continuously.

NOTE
In continuity mode the instrument works in the
same way as the self-diagnostic test.

6.6 Pen light function

(Illuminating the Measurement Point)
Equipped Pen light illuminates the measurement
point in dimly lit area.

►Pressing the Pen light switch turns on the light.

NOTE
●The light is available while the instrument is
powered off.
Using the Pen light shortens the battery life.

7. Battery Replacement

WARNING

Remove the probes from any testing point,
when opening the Battery case.


Batteries are dead when Power LED flashes or
goes off at Self-diagnostic test defined in point
4.1. Follow the procedure below and replace
batteries with new ones(type IEC LR03 1.5V).

►Unlock the Battery case with a coin-shaped

object.



Lock Unlock

►Pull out the Battery case and replace the
batteries. Insert new batteries according to the
engraving on the Battery case.

►Insert the Battery case into the instrument and
firmly lock the case again.

WARNING

Confirm that the Battery case is propely
locked prior to measurements.

8. Specification

Voltage test

Voltage range

12…690V AC/DC

LED (KEW1700 / 1710)

Nominal voltage

12/24/50/120/230/400/690V
AC(45…400Hz), DC(±)

Tolerance
(Threshold voltage)

Light on at more than
: 7±3V (12V LED)
: 18±3V (24V LED)
: 37.5±4V (50V LED)
: 75%±5% of nominal voltage

(120/230/400/690V LED)

Response time

< 0.5s at 100% of each
nominal voltage

LCD (only KEW1710 )

Range / Resolution
(Auto-range)

300V (7.0…299.9) / 0.1V
690V (270…759) / 1V

Accuracy (23±5°C)

±1.5V (7…100V)
±1%±5dgt (100…690V)
AC(45…400Hz), DC(±)

Overrange indication

“OL”

Response time

< 2s at 90% of each voltage

Peak current

Is<3.5mA (at 690V)

Measurement Duty

30s ON (operation time)
240s

OFF (recovery time)

Internal battery

consumption

Approx. 33mA (battery 3V,
measuring 690V AC)

Battery life

Approx. 2500 operations
(30s ON / 240s OFF duty)

Single-pole phase test

Voltage range

100…690V AC (45…100Hz)
180…690V AC (100…400Hz)

Phase rotation test

System

Three-phase 4-wire system
200…690V phase-to-phase
(100…400V earth-to-phase)
AC 50/60Hz

Phase range

120±5 degree

Continuity test

Detection range

0…400kΩ + 50%

Test current

Approx. 1.5μA (battery 3V, 0Ω)

Internal battery

consumption

Approx. 30mA
(battery 3V, 0Ω)

Reference condition

Battery

3V (IEC LR03 1.5V

x

2)

Temperature

-10…55°C operation
-20…60°C storage
No condensation

Humidity

Max 85% RH

Used location

Altitude up to 2000m

Safety

Standard
Category

IEC61010-1, CAT.III /IV 600V
IEC61243-3, CAT.II 690V

Pollution degree

2

IP code

IP65 (IEC60529)

Size

Dimensions

241.5 x 68.5 x 28.5mm

Weight

230g (including batteries)

9. Cleaning and storage

CAUTION

●Use a lightly damp cloth with neutral detergent
for cleaning the instrument. Do not use
abrasives or solvents.
●Do not expose the instrument to the direct sun,
high temperature and humidity or dewfall.
●Put the Probe protection cover on the Tips
while not in use. Otherwise it may cause an

injury.

●Remove batteries when the instrument will not
be in use for a long period.
●Do not install the Battery Case without
batteries.

L2

L3

L1

N

PE

10. For Environment

This instrument is subject to WEEE
Directive (2002/96/EC). Please
contact your dealer near you at
disposal.

DISTRIBUTOR

L3

N

L2

PE

L1

Kyoritsu reserves the rights to change

specifications or designs described in this

manual without notice and without

obligations.

06/2006 92-1873

Advertising
This manual is related to the following products: