<Auto discharge function>

This function allows electric charges stored in the capacitance of

the circuit under test to be automatically discharged after

testing.Discharge can be monitored by the AC voltage reading.

(6) Set the Range switch to the OFF position, and disconnect the

probes from the instrument.

6−3 Continuous measurement

For continuous measurement, a lock-down feature is

incorporated on the Test button. Pressing and turning clockwise

locks the button in the operating position, the button is released

by turning it counterclockwise.

Nominal voltage

0.05

50V

0.1

100V

0.125

125V

0.25

250V

0.5

500V

Lower limit of insulation

resistance to supply

nominal current

(

1mA

)

DANGER

While the Test button is locked down, a high voltage is present

at the tip of a probe. Attention should be paid to avoid possible

shock hazard.

6−4 Output voltage characteristics

This instrument conforms to IEC61557. This standard defines

that the nominal current shall be at least 1mA, and the lower

limit of the insulation resistance maintaining the nominal voltage

at the measurement terminal. (See the graph below.)

This value is calculated by dividing the nominal voltage by

nominal current. i.e., in case that the nominal voltage is 500V,

the lower limit of the insulation resistance is found as follows.

Divide 500V by 1mA equals 0.5MΩ

That is, insulation resistance of 0.5MΩ or more is required

toprovide the nominal voltage to the instrument.