Specification – KYORITSU 3147A User Manual

Page 6

Advertising
background image

― 4 ―

¡

Applicable standards
IEC 61557
IEC 61010-1 Measurement CAT.III 300V/ CAT.II 600V

Protection class II
Location for use: altitude 2000m or less

IEC 61010-031
IEC 60529

IP40

¡

Measuring range and accuracy

<Insulation resistance range>

* Heavy-line circular arc on the scale indicates the primary effective

measuring ranges. (guaranteed accuracy range)

3.Specification

MODEL

Nominal voltage
Max. effective
scale value
Mid-scale value
Accuracy in
primary effective
measuring ranges
Accuracy in
primary effective
measuring ranges
Accuracy at 0
and ∞
Accuracy at
no-load voltage
Nominal current
Short-circuit
current

Response time

3144A

3147A

500V

100MΩ

2MΩ
0.1∼

50MΩ

within ±5% of indicated value

Measuring ranges other than above, 0 and ∞.

within ±10% of indicated value

within ±0.7% of scale length

0%∼ +20% of nominal voltage

1mA 0%∼+20%

Approx. 2mA

Meter reading comes within accuracy within 3 sec.
(It may take time when measuring a capacitive
load.)

250V

50MΩ

1MΩ

0.05∼
20MΩ

125V

20MΩ

0.5MΩ

0.02∼
10MΩ

50V

10MΩ

0.2MΩ

0.01∼

5MΩ

100V

20MΩ

0.5MΩ

0.02∼
10MΩ

3145A

3148A

3146A

3148A