The heart of the power controller is the SCR

(Silicon Controlled Rectifier, also sometimes re-

ferred to as a thyristor).

The SCR has two states, ON and OFF, and allows

current to flow in only one direction when turned

on. SCRs can remain in the off state even though

the applied potential may be several thousand

volts. In the on state, they can pass several thou-

sand amperes. When a small signal is applied

between the gate and cathode terminals, the SCR

will turn on within 10-100 microseconds. Once

turned on, it will remain on until the current through

it is reduced below a very low value, referred to as

the holding current. Since the SCR conducts in

only one direction, two are placed back to back in

an inverse parallel configuration to control AC

current. (Figure 1A.)

Phase-angle: In phase-angle control, each SCR

of the back-to-back pair is turned on for a variable

portion of the half-cycle that it conducts (Figure 1,

B&C). Power is regulated by advancing or delaying

the point at which the SCR is turned ON within

each half cycle. Light dimmers are an example of

phase-angle control.

Phase-angle control provides a very fine resolution

of power and is used to control fast responding

loads such as tungsten-filament lamps or loads in

which the resistance changes as a function of

temperature. Phase-angle control is required if the

load is transformer-coupled or inductive.

The model 1032 is a single-phase, phase-angle, SCR

power controller with features of field adjustable cur-

rent limiting, soft-start and missing cycle detection.

The controller can be ordered to accept command

signals of 0-10Vdc, 0 to 5Vdc, 1-5mA, 4-20mA, or a

potentiometer signal. Models are available for opera-

tion at 120, 208, 240, 377, 480 or 575Vac 50/60 hertz.

The controllers can be obtained with current ratings of

10, 20, 30, 40 or 70 Amps.

The model 1032 linearly controls, with respect to the

command signal, the RMS value of the voltage applied

to the load. The controller also has line voltage

compensation, which, for a constant command sig-

nal, maintains the load voltage constant, independent

of line or supply voltage variations.

The soft-start and missing cycle detection features

set the load voltage to zero on power interruptions of

one half cycle or more, and then increases the load

voltage to the desired value at a predetermined rate.

This feature, on start up or after power failures,

prevents saturation of load transformers. The feature

also eliminates in-rush currents that can occur, due to

loads with a low cold resistance.

Current limiting allows the user to adjust the maxi-

mum current the controller will apply to the load. This

feature is desired when controlling loads such as

silicon carbide, molybdenum disilicide, or other ma-

terials in which the resistance changes with tempera-

ture and/or time.

Electrical isolation of the circuit card and the heat

sink is achieved by the use of an SCR that electrically

isolates the SCRs from its mounting plate, and which

uses photo couplers to isolate the SCR gate signals.

THEORY OF OPERATION:

DESCRIPTION:

MODEL No. IDENTIFICATION:

MODEL NUMBER: 1032-VV-AA-CS(-ILXX)

VV = Rated voltage

12 = 120Vac

24 = 240Vac (For 208 or 220 specify “SC208” or

“SC220”)

48 = 480Vac (for 377 specify “ SC38”)

57 = 575Vac

AA = Rated current capacity 10, 20, 30, 40 or 70 A

CS = Command Signal; The standard controller accepts

a 0 to 5Vdc, a 0 to 10Vdc, or a potentiometer signal.

If the controller has been supplied as a 4/20mA input, a

“-4/20mA” designator will be included in the model

number. An appropriate shunt resistor will be added to

the circuit to provide proper scaling. Check with factory

for other mA input ranges.

The term “ILXX” added to the model number implies that

the current limit will be factory adjusted for the value

specified by “XX”. When the “ILXX” term is not included,

the current limit will be factory set at 105% of the rated

current.

L

O

A

D

Figure 1A. Simplified diagram of an SCR controller

Figure 1B. SCR "ON"

time, shown by shaded

area, is varied to apply

the desired load

voltage.

Figure 1C. Voltage

waveform, as applied

to load.