Replacement parts, Manufactured by, See replacement parts sections – Precision Control Systems 3629C User Manual

Page 26

Advertising
background image

MODEL 3629C

22

04/10/2007

REPLACEMENT PARTS

FUSES

The model 3629C does not have built-in line fuses. It is recommended that the load and controller be protected by using a

class "T" or Semiconductor fuse in each of the three line leads. Bussmann type "JJN" (300 Volts) or "JJS" (600 Volts) are

suitable for up to 600 Amp frames. On frame sizes larger than 600 Amps, a semiconductor type fuse is recommended.

Choose a fuse having a current rating of approximately 120% - 125% of the maximum load current anticipated.

Control Concepts, Inc. stocks a variety of class "T" and semiconductor fuses, as well as fuse blocks and holders, for your

convenience. Consult Control Concepts factory for help to determine the best type and size to protect your application.

Three Bussmann Class CC type FNQ-R time delay fuses are used for transformer and control circuit protection. On

the 120 and 160 Amp units, the transformer protection fuses are accessible from the outside opposite the line and load

connections. On all other units, the fuses are located inside. The orientation of these class CC fuses is important.

Although the fuse may be inserted either way, it will only make contact if oriented in the fuseblock correctly.

REFERENCE DRAWINGS

Firing circuit schematic.

D1001160B

Frame wiring diagram, 50 & 80A.

CS1569A

Frame wiring diagram, 120A.

CS1574A

Frame wiring diagram, 160A.

CS1570A

Frame wiring diagram, 200-425A.

CS1571C

Frame wiring diagram, 500-1000A.

CS1575C

REPLACEMENT SCR’s

Size of controller in Amps (A)

Control Concepts Sub Assembly

50 & 80

SCR/TT91-14

120

SCR/TT105-14

160

SCR/TT132-14

200

SCR/T240-14*

250

SCR/T340-14*

300

SCR/T490-14*

380

SCR/T600-14*

425

SCR/T760-14*

500

SCR/T600-14*

600

SCR/T760-14*

750

SCR/Z1400-14*

1000

SCR/Z1800-14*

* Because of critical assembly requirements, it is recommended that replacement of

SCRs on 200 Amp and larger controllers be done at the factory. If you desire to try

it yourself, request a copy of our technical bulletin concerning replacement of SCR's

on the 3629 controller.

MANUFACTURED BY

7870 PARK DRIVE, CHANHASSEN, MN 55317

TEL: 952-474-6200 FAX: 952-474-6070

TOLL FREE: 800-765-2799

www.ccipower.com U.S.A