Specifications – Precision Control Systems 1029C User Manual

Page 6

Advertising
background image

MODEL 1029C

2

10/19/2007

SPECIFICATIONS

The following specifications apply over an ambient temperature of 0 to 55ºC and a supply voltage of 85% to 110% of the

nominal supply voltage rating.

CONTROL MODE:

Single phase SCR phase-angle control.

FRAME SIZE:

The “[AMPS]A” term within the model number specifies the maximum continuous

RMS current rating at the maximum operating ambient temperature of 55ºC.

RUN COMMAND SIGNAL

AND/OR

IDLE COMMAND SIGNAL:

Command signal

Input Impedance

1/5mA

1200 ohms

4/20mA

300 ohms

0-5Vdc

200K ohms

Potentiometer 200K ohms

(1K, 1/4watt pot recommended for optimum linearity, up to 20K permissible)

The control circuit supplies 5 Vdc to the potentiometer.

Other command signal ranges may be available.

Check with factory for special applications.

If it is desired to use a current command in both the run and idle command

input, the signals must be common sourcing or they must be isolated from

one another. Contact factory for more information.

OPERATING VOLTAGE:

The control transformer installed in this controller has three selectable voltages;

240, 480 & 575 Vac. Other voltages are be available - contact factory for details.

SCR RATINGS:

Peak forward and reverse voltage 1600 volts

SCR SURGE CURRENT

RATINGS :

(peak one cycle

non-repetitive

I

TSM

@ 125°C)

Controller Rating Surge Current Rating

50 & 80 Amp:

1750 Amps Peak

120 Amp:

1900 Amps Peak

160 Amp:

4000 Amps Peak

200 Amp:

4500 Amps Peak

250 Amp:

5200 Amps Peak

300 Amp:

7000 Amps Peak

380 Amp:

10,000 Amps Peak

425 Amp:

13,000 Amps Peak

500 Amp:

10,000 Amps Peak

600 Amp:

13,000 Amps Peak

750 Amp:

16,500 Amps Peak

SCR PROTECTION:

dV/dT rating = 200 volts/microsecond.

dV/dT circuit consists of a capacitor in series with a noninductive resistor. This circuit

is in parallel with the SCRs. The SCRs are protected from voltage transients by a

Metal Oxide Varistor.

RUN/IDLE CONTROL:

A contact closure selects either the run command signal input or the idle command

signal input. See

Figure 10

.

ELECTRICAL CONNECTIONS:

# of LUGS PER LINE/LOAD

CONNECTIONS

Connectors for line and load are provided for copper wire from 6 ga to 250MCM on

controllers rated 50 to 425 Amps.

Connectors for line and load are provided for copper wire from 1/0 to 500MCM on

controllers rated 500 to 750 Amps.

ELECTRICAL ISOLATION:

50-160 Amp heatsink to supply and load voltage: 2500 Volts Peak

200-750 Amp heatsinks are at line voltage potential.

Command signal to supply and load voltage: 1500 Volts Peak