Precision Control Systems 930 User Manual

Page 25

Advertising
background image

Model 930 ControlIR

TM

Instruction Manual

Dimensions and Specifications

Research, Inc.

Page 21 of 25












Wiring Specifications

Electrical Isolation:

Heat sink to supply and load voltage: 2500 Volts peak.
Command signal to supply and load voltage: 1400 Volts peak.

Slew Rate:

200 ms. Slew rate is the time required for the load voltage to change 63% of the
value represented by the command signal. The current limiting action will affect
the slew rate if the load current is greater than the current rating of the SCRs.



Wire Ratings:

Wire Temperature Rating:

75

°C or Higher

Line/Load Wiring Voltage Rating (240 VAC systems)

300 VAC Minimum

Line/Load Wiring Voltage Rating (480 VAC systems)

600 VAC Minimum

Control Wiring

300 VAC Minimum

Allowable Wire Sizes:

Current

Rating of

System

Line

Connections

Load

Connections

Ground

Connection

Control

Circuit

Connections

120 Amp
160 Amp

#6-250 MCM
#6-250 MCM

#6-250 MCM
#6-250 MCM

#4-1/0 AWG
#4-1/0 AWG

22-10 AWG
22-10 AWG


Recommended Minimum Wire Sizes:

NOTE:

Wire temperature and connector ampacity ratings are based on NEC table 310-16
using 75

°

C copper wire derated for 50

°

C ambient environment.

Current

Rating of

System

Line

Connections

Load

Connections

Ground

Connection

Control

Circuit

Connections

120 Amp
160 Amp

1 AWG

2/0 AWG

6 AWG
4 AWG

6 AWG
6 AWG

16 AWG
16 AWG


Electrical Inputs:

Heater open interlock switch

Contacts Rated for 120 VAC at 2.0 A

Cooling flow interlock switch

Contacts rated for 120 VAC at 100 mA

Heater over-temp. thermo-switch

Contacts rated for 120 VAC at 100 mA

Remote interlock switch

Contacts rated for 120 VAC at 100 mA

Advertising