Wiring connections – Precision Control Systems 930 User Manual

Page 9

Advertising
background image

Model 930 ControlIR

TM

Instruction Manual

Operating Instructions

Research, Inc.

Page 5 of 25

WIRING
CONNECTIONS






Table 3-1 Wiring Specifications



































Conduit entry into the system should be made near the right side of the cabinet for
power wiring, near the center of the cabinet for load wiring, and near the left side for
low voltage control wiring. Assure that metal fragments are not allowed to fall into the
equipment while holes are made for conduit fittings.

We suggest a separate conduit entry should be made for low level DC control wiring if
used. This includes the remote setpoint input or thermocouple wire (temperature
control option).

Wire Ratings:

Wire Temperature Rating:

75

°C or Higher

Line/Load Wiring Voltage Rating (240 VAC systems)

300 VAC Minimum

Line/Load Wiring Voltage Rating (480 VAC systems)

600 VAC Minimum

Control Wiring

300 VAC Minimum

Allowable Wire Sizes:

Current

Rating of

System

Line

Connections

Load

Connections

Ground

Connection

Control

Circuit

Connections

120 Amp
160 Amp

#6-250 MCM
#6-250 MCM

#6-250 MCM
#6-250 MCM

#4-1/0 AWG
#4-1/0 AWG

22-10 AWG
22-10 AWG


Recommended Minimum Wire Sizes:

NOTE:

Wire temperature and connector ampacity ratings are based on NEC 310-16 using
75

°

C copper wire derated for 50

°

C ambient environment.

Current

Rating of

System

Line

Connections

Load

Connections

Ground

Connection

Control

Circuit

Connections

120 Amp
160 Amp

1 AWG

2/0 AWG

6 AWG
4 AWG

6 AWG
6 AWG

16 AWG
16 AWG

Electrical Inputs:

Heater open interlock switch

Contacts Rated for 120 VAC at 2.0 A

Cooling flow interlock switch

Contacts rated for 120 VAC at 100 mA

Heater over-temp. thermoswitch

Contacts rated for 120 VAC at 100 mA

Remote interlock switch

Contacts rated for 120 VAC at 100 mA

Advertising