2 output, Output signal, Failure information – Pyromation T82 User Manual

Page 34: Load, Linearization/transmission behavior, Mains voltage filter

Advertising
background image

Technical data

T82

34

The following connection combinations are possible when both sensor inputs are assigned:

Sensor input 1

Sensor input 2

RTD or

resistance

transmitter, 2-

wire

RTD or

resistance

transmitter, 3-

wire

RTD or

resistance

transmitter, 4-

wire

Thermocouple

(TC), voltage

transmitter

RTD or resistance
transmitter, 2-wire

4

4

-

4

RTD or resistance
transmitter, 3-wire

4

4

-

4

RTD or resistance
transmitter, 4-wire

-

-

-

-

Thermocouple (TC),
voltage transmitter

4

4

4

4

12.2

Output

Output signal

Analog output

4 to 20 mA, 20 to 4 mA (can be inverted)

Signal encoding

FSK ±0.5 mA via current signal

Data transmission rate

1200 baud

Galvanic isolation

U = 2 kV AC (input/output)

Failure information

Failure information as per NAMUR NE43:
Failure information is created if the measuring information is missing or not valid. A complete list
of all the errors occurring in the measuring system is created.

Underranging

Linear drop from 4.0 to 3.8 mA

Overranging

Linear increase from 20.0 to 20.5 mA

Failure, e.g. sensor breakage; sensor short circuit

≤ 3.6 mA ("low") or ≥ 21 mA ("high"), can be selected
The "high" alarm setting can be set between 21.6 mA and 23 mA,
thus providing the flexibility needed to meet the requirements of
various control systems.

Load

R

b max.

= (U

b max.

- 11 V) / 0.023 A (current output)

U

b

42 V

1348

1098

250

11 V

0

36.25 V

16.75 V

Supply voltage (V DC)

Load ( )

A0014066-EN

Linearization/transmission
behavior

Temperature-linear, resistance-linear, voltage-linear

Mains voltage filter

50/60 Hz