Operating menu and parameter description

61

Failure current

Navigation

Setup ® Advanced setup ® Current output® Failure current
Expert ® Output ® Failure current

Prerequisite

The Max. option is enabled in the Failure mode parameter.

Description

Use this function to set the value the current output adopts in an alarm condition.

User input

21.5 to 23.0 mA

Factory settings

22.5

Current trimming 4 mA

Navigation

Setup ® Advanced setup ® Current output® Current trimming 4 mA
Expert ® Output ® Current trimming 4 mA

Description

Use this function to set the correction value for the current output at the start of the measuring
range at 4 mA (® ä 59).

User input

3.85 to 4.15 mA

Factory settings

4 mA

Current trimming 20 mA

Navigation

Setup ® Advanced setup ® Current output® Current trimming 20 mA
Expert ® Output ® Current trimming 20 mA

Description

Use this function to set the correction value for the current output at the end of the measuring
range at 20 mA (® ä 59).

User input

19.850 to 20.15 mA

Factory settings

20.000 mA