4 Configuration parameters

External
cold junction
temperature

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ Ext. CJ temp.

-50 to +150°C

External cold junction
temperature for
thermocouples

Range
start

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ Range start

any value

0mA

Range
end

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ Range end

any value

20mA

Start temperature

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ Start

temperature

any value

Only for sensor: current or
voltage with linearization,
resistance thermometer,
thermocouple.
Only for signals that have
not yet been linearized.

End temperature

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ End temperature

any value

Only for sensor: current or
voltage with linearization,
resistance thermometer,
thermocouple.
Only for signals that have
not yet been linearized.

Scaling start

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ Scaling start

-99999 to 0 to +99999

Scaling end

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ Scaling end

-99999 to +100 to +99999

Filter constant

Configuration
➔ Analog inputs

➔ Analog input 1—6

➔ Filter constant

0.0 — 0.1 — 10.0s

Parameter

Value/Selection

Description