3.3.1 Form 1 Message

The master device sends a Form 1 message to ascertain whether a specific

communications address is occupied by an instrument. If there is an instrument at

that address, a reply (with a positive acknowledgement) is received. If there is no

instrument at that address or if there is a communications link failure, no reply is

received. The message from the master device is of the form:

Laa??*

where aa is the address (a two-digit hexadecimal number). The reply from the

addressed instrument is of the form:

Laa?A*

where aa is the same address as in the received message.

3.3.2 Form 2 Message

This message implements a Parameter Read operation. The message from the

master device is of the form:

Laap?*

where

aa is the address (a two-digit hexadecimal number)

p is a single-character parameter identifier (see Table 3-1)

The reply, if the Parameter Read operation is successful, is of the form:

LaapnnnnnA*

where

aa is the same address as in the received message

p is a single-character parameter identifier (see Table 3-1)

nnnnn is the data (a five-digit hexadecimal number)

If the specified parameter is invalid (e.g. not applicable to the addressed

instrument), the reply is of the form:

Laap00000A*

where

aa is the same address as in the received message

p is a single-character parameter identifier (see Table 3-1)