Installation & Maintenance : 6564868 02/2013

Commissioning Data

GENERAL DATA

Operating limits

(For 100% Water)

Standard Unit

Minimum Ambient Air DB °C

-20°C

Maximum Ambient Air DB °C at Full Load Operation

40°C

Maximum Ambient Air DB °C at Reduced Load Operation

45°C

Minimum Leaving Water Temperature °C

+5°C

Maximum Return Water Temperature °C

+20°C

Minimum / Maximum

ΔT

4°C / 8°C

1

For conditions outside those quoted, please refer to Airedale.

2

For minimum ambient, it is assumed that adequate freeze protection is fitted.