Commissioning Data
GENERAL DATA
Operating limits
(For 100% Water)
Standard Unit
Minimum Ambient Air DB °C
-20°C
Maximum Ambient Air DB °C at Full Load Operation
40°C
Maximum Ambient Air DB °C at Reduced Load Operation
45°C
Minimum Leaving Water Temperature °C
+5°C
Maximum Return Water Temperature °C
+20°C
Minimum / Maximum
ΔT
4°C / 8°C