At power up, if a user does a configuration read before sending a configuration

as is the case when auto configuring the network, this default configuration

will be sent.
If during operation, after the unit has been configured, the unit is queried for its

configuration it will send the current configuration. If a power cycle occurs the

unit will return to the default configuration until it is again configured.

4.3 Data Exchange

Once a correct configuration telegram has been received the unit will enter

data exchange mode. In this mode input telegrams will be sent whenever

new data is available and output telegrams will be processed as they are

received. If communication is lost during data exchange, the unit will return to

wait parameterization mode.

4.3.1 Data In Telegram (To Master)

The data in telegram from the unit can contain any combination of process

variables, gas string, and status byte. In the case of a controller, the PID

variables can be configured to be read to allow tuning of the control loop.

4.3.1.1 Process variables

Each of the process variables are 4 bytes long and formatted in big endian

IEEE 32 floating point. If the meter/controller doesn’t support a value it will

always be zero.
All the reading values are in the engineering units specified at time of order

(for example: with a 200SLPM controller the mass flow will be SLPM).

4.3.1.2 Gas String

Gas is a null terminated string that has 8 bytes. If the gas specified is less than

7 characters long, the gas string will be in the leading octets and be followed

by zeros (nulls).

4.3.1.3 Status Byte

The status is a byte that contains active high bits in the following bit format:

0000TMVP
Where:

T – Totalizer Rollover

M – Mass Over Range

V – Volumetric Over Range

P – Pressure Over Range

4.3.1.4 PID variables

For controllers, a special tuning configuration could be made and the values for

the PID loop gains will be reported here. They can be set using the command

module of the data out telegram.