Alicat PROFIBUS User Manual

Page 7

Advertising
background image

7

4.3.2.3 Command

The command consists of four octets — where the first two octets are the

command and last two octets are the data that applies to the command. Both the

command and data are 16 bit unsigned integers that are in big endian format.
Current commands are:

Command

Action

0 (0x0000)

Do Nothing

21 (0x0015)

Change P in PID loop

22 (0x0016)

Change D in PID loop

23 (0x0017)

Change I in PID loop

46 (0x002E)

Change Gas Select

65 (0x0041)

Change Power Up Set-point Configuration

Note: Command values not listed in the above table are reserved for factory

use only and can cause undesired effects if utilized.
For the data bytes the following are valid:

Valid Values

Data Type

0 to 65535 (0x0000 to 0xFFFFF)

PID Parameters

0 to 29 (0x0000 to 0x001D)

Gas Parameter

0, 32768, or 49152 (0x0000,0x8000,

or 0xC0000)

Power Up Set-point

Configuration

Description of power up set-point configuration bits:

Valid Values

Meaning

0 (0x0000)

Unit will go to zero set-point at power up or loss of

Profibus communication.

Also the unit will respond to set-points given over the

Profibus

32768 (0x8000)

Unit will maintain last set-point saved to

nonvolatile memory at power up or loss of Profibus

communication (see section 4.3.2.2 Control

Register)

49152 (0xC000)

Same as 32768 with the addition that unit will ignore

Profibus set-points.