Flow sensor inputs, Specifications – Badger Meter 3050 Series Btu Monitor User Manual

Page 29

Advertising
background image

Page 29

6-11

Installation & Operation Manual

FLOW SENSOR INPUTS

Type

Threshold

Signal Limit

Frequency

Pull-up

Impedance

Aux. Power

Calibration

Pulse-Di

2.5 VDC

30VDC

0.4 Hz to

10kHz

1K to12VDC

12VDC@30mA

K + Offset

Pulse-K Factor

2.5 VDC

30VDC

0.4 Hz to

10kHz

12VDC@30mA

Pulse/Gal

Pull-up-K Factor

2.5 VDC

30VDC

0.4 Hz to

10kHz

1K to12VDC

12VDC@30mA

Pulse/Gal

Analog – 4-20mA

50mA Fused

100 Ω

12VDC@30mA

Pulse/Gal

Analog – 0-20mA

50mA Fused

100 Ω

12VDC@30mA

Linear

Analog – 0-1 VDC

30VDC

100 Ω

12VDC@30mA

Linear

Analog – 0-5 VDC

30VDC

100 Ω

12VDC@30mA

Linear

Analog – 0-10 VDC

30VDC

100 Ω

12VDC@30mA

Linear

Rate Units of Measure: GPM; gal/sec; gal/hr; Mgal/day; LPS; LPM; LPH; ft3/Sec; ft3/min; ft3/hr;m3/sec; m3/min; m3/hr; acre-ft/sec; acre-ft/min; acre-ft/hr; bbl/sec; bbl/min; bbl/hr;

and field programmed custom units 0.00 to 999999999

Total Units: gallons; Mgal; liters; ft3; m3; acre-ft; bbl; and field programmed custom units 0.00 to 999999999

SPECIFICATIONS

Voltage
12-24 VDC / VAC
(Limit: 8-35VDC)
(Limit: 8-28VAC)

DC current draw (~280mA)
AC power rating (~5 VA)

Display
16 character by two-line alphanumeric
dot matrix 7.95mm high backlit LCD

Operating Temperature
-20°C to +70°C
Storage Temperature
-30°C to +80°C

Dimensions
Panel Mount:
3.78"W x 3.78"H x 3.23"D
(96mm x 96mm x 63mm)
Wall Mount:
4.80"W x 4.72"H x 3.63"D
(120mm x 120mm x 92mm)
Weight:
panel mount 12 oz

Pulse and Relays
Both pulse and relay are fully functional as either
totalizing, or Set Point outputs.

Pulse Electrical
1 Amp @ 35VDC/ 30VAC
Closed: 0.5Ω @ 1 AMP Open: >10

8

Relay Electrical
Resistive load: 5Amp@120VAC/30VDC
Inductive load: 1Amp@120VAC/30VDC

Pulse/Unit Volume (Totalizer)
Driving Source:
flow total; Btu total
Units: any predefined or custom unit
Rate: 1 Pulse per 1.0000000 to 99999999 units
Contact Time: 1 to 9999 mS

Set Point (Alarm)
Driving Source:
flow rate; Btu rate;

temperature 1; temperature 2, delta T
Units: Any predefined or custom unit
Set Point : 1.0000000 to 999999999
Delay to Set: 1 to 9999 Seconds
Release Point: 1.0000000 to 999999999
Delay to Release: 1 to 9999 seconds

Optional Analog Output
Driving Source:
flow rate; PID control
Range: 4-20mA; 0-20mA (isolated current sinking
or sourcing)
Sinking: 30VDC @ 0mA maximum; 3 volts
@20mA minimum
Sourcing: 600 W maximum load

USB Communication
Provides complete access to all programming and
operation features.
Requirements:
USB 2.0 A to Mini-B 5-Pin Cable
(Example: SYSONIC model UAM56 GWT/B)

RS-485 Communication
Supports: Modbus and BACnet/MSTP

Accessories
Programming kit
Wall mount kit

Example:

3050

-

x

x

Series

BTU

3050

Option - Analog Output, RS485 (BACnet / Modbus), and USB

No Option

0

Analog Output, RS485 with BACnet and Modbus, and USB

1

Option - Mounting

Panel Mount

0

Wall Mount

1

Figure 21: Series 3050 Ordering Matrix