Series 3050 Btu Monitor

Wall Mount Installation

The Series 3050 wall mount is designed to mount onto a wall with four bolts or screws. The mounting hole pattern and box

dimensions for the Series 3050 NEMA4 waII mount are shown in Figure 2.

Figure 2: Wall Mount and Dimensions

Electrical Installation

Power Supply Wiring

The Series 3050 Btu Monitor requires 12-24 VDC/VAC to operate. Check the Specifications on page 29 for DC current draw

and AC Volt-Amp requirements.

A fused circuit is always recommended.

Connect the positive of the power supply to the Series 3050 terminal marked (ACL/DC+), and connect the negative of the

power supply to the Series 3050 terminal marked (ACC/DC-).

If a Badger Meter Data Industrial plug-in power supply (Model A1026, A-503) is being used, connect the black-white wire to

the terminal marked (ACL/DC+) and the black wire to the terminal marked (ACC/DC-).

Figure 3 ( Power Supply Wiring)

(+) (-)

12-24VDC

Power

Supply

( Line) (Com)

12-24VAC

Power Supply

OR

Earth

or

Panel

Ground

Ground wire should be heavy gauge and as short as possible

Earth

3

LV AC/DC(-) 2

LV AC/DC(+) 1

POWER

Figure 3: Power Supply Wiring