13

MGE™ Galaxy™ 300 10-40 kVA 3:3, 10-30 kVA 3:1 - 380/400/415 V Installation

Specifications

Battery Output

Recommended Cable Sizes

Caution: All wiring must comply with all applicable national and/or electrical codes.

Note:
AC cable sizes are determined for:
- the TNS system for copper, single-core cables, type U1000 R02V, 100 m long with a line
voltage drop <3%, installed on perforated cable trays, XLPE-type insulation, single-layer
trefoil formation, THDI between 15% and 33%, 35°C, at 400 V, grouped in four touching
cables.
Battery cable sizes are determined for:
- copper, single-core cables, type U1000 R02V, maximum length 25 m with a line voltage
drop <1%.

Battery Description

Nom voltage (V)

12 v/block

I

Nom

discharge

1

See the battery input table in the UPS installation manual 990-3618

I

Max

discharge

2

See the battery input table in the UPS installation guide 990-3618

End Voltage

9.9 v/block

1

Nominal battery discharge current based on rated load and nominal battery voltage.

2

Maximum battery discharge current based on rated load at the end of the discharge.

3:3

3:1

kVA

10

15

20

30

40

10

15

20

30

min max min max min max min max min max min max min max min max min max

Mains input (mm²)

10 35

10 35 10 35 16 35 25 35 10 35 10 35 10 90

16 90

AC output (mm²)

10 35

10 35 10 35 16 35 25 35 10 35 25 35 35 90

70 90

Battery (mm²)

10 35

10 35 16 35 25 35 35 35 10 35 10 35 16 25

25 35

Bypass (mm²)

10 35

10 35 10 35 16 35 35 35 10 35 25 34 35 90

70 90