MPM, APM, PPM, & LTI Series Modbus

®

Register Tables

Serial Communication

Page 6

Register

1

Name Access

Limits or

Range

2

Units

Data

Type

3

Function

Code(s)

Comments

Number Address

(hex)

40040

39

(0027)

Stop Batch

Write Only

Not applicable

None

Bit

06, 16

Set bit to 1 to pause the batch process; set bit to 1 again to stop
batch process.

40041

40

(0028)

Alarm

Acknowledge

Write Only

Not applicable

None

Word; Bits

06, 16

Clear Relay n alarm condition. Set bit equal to 1 to
acknowledge. Only has effect on relays programmed to allow
manual acknowledging. Bits 0-7 mirror Bits 8-15, Alm = Alarm

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Alm

8

Alm

7

Alm

6

Alm

5

Alm

4

Alm

3

Alm

2

Alm

1

Alm

8

Alm

7

Alm

6

Alm

5

Alm

4

Alm

3

Alm

2

Alm

1

40042

41

(0029)

Reset Maximum

Display value

Write Only

Not applicable

None

Bit

06, 16

Set bit to 1 to reset the Maximum Display value.

40043

42

(002A)

Reset Minimum

Display value

Write Only

Not applicable

None

Bit

06, 16

Set bit to 1 to reset the Minimum Display value.

40044

43

(002B)

Reset Maximum

/Minimum Display

value

Write Only

Not applicable

None

Bit

06, 16

Set bit to 1 to reset the Maximum/ Minimum Display values.

40045

44

(002C)

Reset Total value Write Only

Not applicable

None

Bit

06, 16

Set bit to 1 to reset the Total value.

40046

45

(002D)

Reset Grand

Total value

Write Only

Not applicable

None

Bit

06, 16

Set bit to 1 to reset the Grand Total value.

40047

46

(002E)

Reset Batch

Count value

Write Only

Not applicable

None

Bit

06, 16

Set bit to 1 to reset the Batch Count value.

40048

47

(002F)

Reserved for future use.

40049 – 40050

48 – 49

(0030 – 0031)

Reserved for future use.

40051

50

(0032)

Control Mode

Read Write

Not applicable

None

Bit

03, 04,

06, 16

0 = auto, 1 = manual

40052

51

(0033)

Manual Control

Analog Output

Setting

Read Write

0 to 23999

μA Integer

03, 04,

06, 16

Represents the Manual Control Analog Output value.
Note: Register 40051 must be set to 1 = manual mode for
registers 40052-40069 to take effect.

40053

52

(0034)

Reserved for future use.

40054

53

(0035)

Manual Control
Relay 1 Setting

Read Write

Not applicable

None

Bit

03, 04,

06, 16

Represents the Manual Control Relay 1 setting. 0 = off, 1 = on