Emergency stop and safety gate monitoring relays

with time-delay function

DEVICE

SAFE T…

Emergency stop and safety gate monitoring relay with immediate and

APPLICATIONS

delayed outputs

APPROVALS

CE, TÜV, UL, C-UL

CONTACTS

2 n.o., 2 n.o. start up delayed, 1 n.c.

cross circuit protection or single-channel

SPECIAL CHARACTERISTICS

Time delay 0,05s - 600s in 64 steps,

automatic or manually start with start button

LED

Power, channel 1, cannel 2, channel 1 and channel 2 time-delayed

OPERATING VOLTAGE

24 V AC / DC ( + 25 - 20 % ) (electronic fuse )

POWER CONSUMPTION

ca. 4,8 W

START UP DELAY / FALLBACK TIME

< 400ms / < 30 ms / adjustment

CONTACT CAPACITY max.

6 A , 250 V AC, 24 V DC

CONTACT CAPACITY min. at 24V DC (*)

6 mA

SIMULTANEITY

SAFE TN: 1s / SAFE TA,TR: 3s / TU: infinite

ENVIRONMENTAL TEMPERATURE

- 25°C to + 55°C

SWITCHING CAPACITY

1500 VA (resistive load)

CONTACT SECURITY

3,6A

OPERATING MODE

(*) We offer all devices who have a CONTACT

CAPACITY of min. 100 mA at 24 V DC with

hard gold-plated contacts. In this way the

CONTACT CAPACITY of min. 100 mA is only 4 mA.

Please ask our sales team!

CONNECTION DIAGRAM

When releasing E-Stop button or opening the safety gate (E-Stop circuit are

open) the contacts 13-14 and 23-24 (outputs) open. The contacts 47-48/57-

58 open delayed at the adjusted time.

SAFE TN standby time after applying of the supply voltage < 0,95 s.

Opening of

the E-Stop circuits meanwhile results to failure.

SAFE TA standby time after applying of the supply voltage < 0,95 s.

Opening of

the E-Stop circuits meanwhile results to several activations of the

outputs after the standby time.

SAFE TR restart is possible during standby time.

SAFE TU standby time after applying of the supply voltage < 0,95 s.

Opening of

the E-Stop circuits meanwhile results to several activations of the

outputs after the standby time.

S33 S34

S11 S12

Not-Halt

E-Stop

Start

S22

S21

FUNCTION CIRCUIT DIAGRAM

Power

Logic

A1 S35 S10 S11 S12 13 23 31

47

57

58

48

32

24

14

S22

S21

S34

S33

A2

K1

K2

K3

K4

~=

t = 0,05s....600s

Certifications according to

Safety relevant substance data

Depending on wiring (only max. values are given)

EN ISO 13849-1 / EN 62061: PLe, Cat. 4 / SIL3, SIL CL3

PFH: 3,4*10

-9 1

/

h

, PFD: 9,32*10

-6 1

/

h

, SFF: 94%

MTTFd: >100 years / high, DC: 99% / high, CCF: achieved