Guarding

The connections that are made to this unit are
high amperage. Ensure the protective rubber boots
are properly installed, followed by the provided
protective cover.

Note: Rubber boots are removed for clarity.

Start Up

Upon startup, the condition of the
LED indicators should resemble
this photo. The Engine battery has
been given priority, the alternator
is charging and the system is on.

Installation

Fuses/over current protection

General - The fuses can be up to 150% of the maximum output of the alternator. Each
conductor must be fused with the exception of the starting circuit, which is not required
to be fused.

Alternator – If the alternator is self-regulating and the conductor is 40 inches or shorter and
protected in a sheath or split-loom it does not require a fuse. If its longer than 40 inches a
fuse is required.

Connections

Large AWG conductors require specific tools to make a safe, reliable crimp when attaching
ring terminals. It is recommended that pre-terminated cables be purchased or the proper
tool be used.

Solder is not an acceptable connection for ring terminals. Soldering causes a brittle
connection which will break over time due to the flexibility of the stranded cable and normal
vibration in a boat.

When bolting the ring terminal to the stud, ensure the ring terminal is installed first, then the
flat washer followed by the lock washer.

9

NOTE: This diagram has all of the elements of the ProIsoCharge models. Additional alternators
or charging inputs will follow the same basic configurations.

Installation

Priority MGNT

High VDC
High VDC

Charging

Charging

Charging

Low VDC
ON

Standby
System ON

SYSTEM STATUS

Adv. Reg.

ProIsoCharge

1

3

Intelligent Alternator Distribution System

0.0 VDC Drop - Battery Isolation & Charging

Ignition

DC

Input

Distributed-On-Demand

Sensing

Engine Battery Priority & Protection

Waterproof to IP66

3

2

ENG

1

3

2

ENG

1

Battery
Alternator
Flashing
ON

Digital

ProMar

Performance Charging

Battery
Switch
Bank 2

Battery
Switch
Start

Fuse

12V Battery 2 Bank

12V Battery 3 Bank

Parallel Batteries (12V)
For a 12V Bank
(Increases the Amp/Hr Capacity)

Starter

Alternator

Engine

To

Ignition

To Battery Senses Alt or Regulator

Fuse
(see note)

Battery
Switch
Bank 3

To Engine Negative or Bus

3

4

2

1

Advertising