Electrical connections

The power supply has to be connected to

and

.

is considered as

system ground. If the analogue output is connected to a controller the same ground
reference has to be used for
the CF8-W-Disp-GH unit and for the control system!
Unless different transformers are used, special precautions need to be taken.


PLEASE NOTE! The CF8-W-Disp-GH
signal ground is not galvanically
separated from the CF8-W-Disp-GH

power supply!

NOTE!
The same ground reference has
to be used for the CF8-W-Disp-GH

unit and for the control system!

Connect the power after mounting. The
analogue output should be connected before
measuring.

Connection

Terminal

Function

Electrical Data

Remarks

Power (+)


Power ground

(-)

24 VAC/DC+ (+-20%),

3W

24 VAC/DC-

2W without output load


See note 1!

Out(1)




Out(2)

Analogue

Output 1 (+)


Analogue

Output 2 (+)

0-10 VDC or 0-20 mA,
2-10 VDC or 4-20 mA,



0-10 VDC or 0-20 mA,

2-10 VDC or 4-20 mA

According to positions of
OUT1 and start point
jumpers.
See note 2

!


According to positions of
OUT2 and start point
jumpers.
See note 2

!

5


6

7

Normally

closed relay

Relay COM

Normally open

relay

Contact free relay

minimum load 1mA/5V

rated load 0,5A/125VAC;

1A/24VDC

Triggered by register
OUT(3)

8

Not used

Table 1: Electrical connections

~

+

~

+