6

Electrical installation

6.1 General wiring guidelines


Power supply wiring


Heavy machinery and instrumentation should not share the same power supply wiring. If this cannot be
avoided, noise filters and surge protectors should be used. Most UPS devices have those features already
integrated.


General guidelines for signal cables


The following guidelines are derived from European Standard EN 50170 for the transmission of signals by
copper wires. When planning an installation, the rules provided by EN 50170 should be followed under
consideration of local circumstances to determine the position of machines and equipment.

All ROTRONIC products are tested for Electromagnetic Compatibility according to EMC Directive
2004/106/EG and following European standards:

-

EN 61000-6-1: 2001, EN 61000-6-2: 2005

-

EN 61000-6-3: 2005, EN 61000-6-4: 2001 + A11


Whenever the level of electromagnetic interference is expected to be high, both the instruments and signal
cables should be placed as far away as possible from the source of interference.

In general, signal cables should be installed in bundles or channels / conduits, separate from other cables as
indicated in the table below:

Bus signals such as RS485

Data signals for PCs, printers etc.

shielded analog inputs

unshielded direct current (<= 60V)

shielded process signals (<= 25 V)

unshielded alternate current (<= 25V)

coaxial cables for CRT monitors

in common bundles or channels / conduits

direct current from 60 V to 400 V
(unshielded)

alternate current from 25V to 400 V
(unshielded)

in separated bundles or channels /
conduits, without minimum distance

direct and alternate current > 400 V
(unshielded)

Telephone lines

lines leading into EX-rated areas

in separated bundles or channels /
conduits, without minimum distance