2 guidelines for rs-485 wiring, 3 cable grip and cable specifications, 4 wiring – ROTRONIC HF8 User Manual

Page 15: 1 electrical diagrams, Guidelines for rs-485 wiring, Cable grip and cable specifications, Wiring, E-m-hf8-v2_10

Advertising
background image

E-M-HF8-V2_10

Rotronic AG
Bassersdorf, Switzerland

Document code

Unit

HygroFlex HF8 Humidity Temperature
Transmitter: User Guide

Instruction Manual

Document Type

Page 15 of 35

Document title

© 2012; Rotronic AG E-M-HF8-V2_10

direct and alternate current > 400 V
(unshielded)

Telephone lines

lines leading into EX-rated areas

in separated bundles or channels /
conduits, without minimum distance

Lightning protection


Cabling in areas with a risk of lightning requires a lightning protection. For cabling underground in between
buildings, we recommend the use of special fiber optic cables. If this is not possible, use copper cables that
are suitable for underground installation.

6.2 Guidelines for RS-485 wiring


See document E-DV04-RS485.01: RS485 Network Installation and Start-up Guidelines

6.3 Cable grip and cable specifications

The HF8 is supplied either with one M16 sealing cable grip or with a ½” conduit adapter. The M16 cable grip
provides effective sealing only with cables having the proper outside diameter. Preferably, use a cable with an
outside diameter of 6 to 7 mm (0.236 to 0.275 inch) with 18 AWG wires.

6.4 Wiring

6.4.1

Electrical diagrams


Note: the following diagrams apply to the HF8 with any of the galvanically isolated power supply options.

HF8 analog voltage outputs

The maximum permissible cable length can be determined under consideration of the voltage drop caused by
the current flowing to the devices connected to the unit. The voltage drop in the cable depends both on cable
resistance and on the equivalent resistance of the devices connected in parallel to the unit. The total
resistance connected to each unit output should be at least 1000 ohms. Cable resistance should not be more
than 1/1000 of the load resistance.