3.0 ELECTRICAL INSTALLATION

To access electrical connections remove cover on top of the Model 230

for ce compliance a shielded cable with both ends properly grounded is required.

3.1 Voltage output Units

The Model 230 is a 3-wire circuit with three terminals available for wiring. The -Excitation and -Output are commoned on

the circuit.

Input Power

The 230 can operate from either 9-30 VDC for 0-5 VDC output version or 13-30 VDC for 0-10 VDC output version

Excitation Connected to positive terminal of DC Power Supply

COM

Connect as the reference for power supply and output signal

OUT

Connect to positive terminal of Control or Pressure Monitor

3.2 current output Units

Model 230 (current output) transducers are true 2-wire, 4-20 mA current output devices and deliver rated current into any

external load of 0-1000 ohms.

The 4-20 mA current output units are designed to have current flow in one direction only. PLEASE OBSERVE POLARITY.

We suggest that an electrical cable shield be connected to the system’s loop circuit ground to improve electrical noise

rejection.

MIN Supply Voltage:

9 + .02 x (Resistance of receiver plus line)

MAX Supply Voltage:

30 + .004 x (Resistance of receiver plus line)

For voltage output, use COM,OUT

and EXC terminals

For current (4-20 mA) output,

use + and - terminals

Diagram 1

Power Supply

Load

(Monitor)

Setra

Transmitter

(4-20 mA)

+

+

+