5

PSI

5 VDC Full Scale Outputs

10 VDC Full Scale Outputs

Compound

0.2 to 5.2

0 to 5 VDC

0.2 to 10.2

0 to 10 VDC

Range

Voltage (VDC)

Voltage (VDC)

Voltage (VDC)

Voltage (VDC)

(Factory Set to within

±25mV)

(Factory Set to within

±50mV)

-14.7 to 25

2.051

1.851

3.903

3.703

-14.7 to 50

1.336

1.136

2.472

2.272

-14.7 to 100

0.841

0.641

1.482

1.282

-14.7 to 250

0.478

0.278

0.755

0.555

-14.7 to 500

0.343

0.143

0.486

0.286

-14.7 to 1000

0.272

0.072

0.345

0.145

-14.7 to 3000

0.224

0.024

0.249

0.049

Bar

5 VDC Full Scale Outputs

10 VDC Full Scale Outputs

Compound

0.2 to 5.2

0 to 5 VDC

0.2 to 10.2

0 to 10 VDC

Range

Voltage (VDC)

Voltage (VDC)

Voltage (VDC)

Voltage (VDC)

(Factory Set to within

±25mV)

(Factory Set to within

±50mV)

-1 to 1.7

2.052

1.851

3.904

3.704

-1 to 3.4

1.336

1.136

2.473

2.273

-1 to 7

0.825

0.625

1.450

1.250

-1 to 17

2.494

0.278

0.756

0.556

- 1 to 35

0.339

0.139

0.478

0.278

-1 to 70

0.270

0.070

0.341

0.141

-1 to 200

0.225

0.025

0.250

0.050

4.1 Voltage Output Zero Adjustment

While monitoring the voltage between the positive output (+OUT) and
common (COM), and with the pressure port open to atmosphere, or with zero
pressure applied, the zero may be adjusted by turning the zero potentiometer
screw.

For the 5 VDC Full Scale Output, the tolerance on zero and span settings is
±25mV. For the 10 VDC Full Scale Output, the tolerance on zero and span
settings is

±25mV. For absolute pressure ranges, the zero should be adjusted

with a full vacuum applied. See Diagram 5 for nominal “installed” output at
atmospheric pressure for compound pressure ranges.

NOMINAL “INSTALLED” OUTPUT AT ATMOSPHERIC PRESSURE

Setra

Transducer

Power

Load

+

+

_

+

_

_

Diagram 5

Diagram 4