Setra System SRPM User Manual

Page 12

Advertising
background image

12

1. V Out: 0 to 5, 0 to 10 VDC

2. C Out: 4 to 20 mA

3. Common

Receiver

(V)

+

Voltage Output

3.3.5 BACnet
BACnet hardware is implemented as isolated RS485. Wire to Connector
J2, labeled RS-485. Connect tx line to +(A), rx to –(B) and ground wires
to S. Connect Shields together with wire nut.

Hardware confi guration is done using a 5 position dip switch (S1) located
in the upper right hand section of the PCBA as well as through the touch
screen interface, see Section 4.4. and 4.9.

Position

Function

1

MAC address enable

2

N/C Not Connected

3

Pull Up Resistor

4

Termination Resistor

5

Pull Down Resistor

Use a small fl at blade screwdriver or pen to push the switch to the right
to turn that function on, otherwise it is off.

There is a BACnet setup screen that is enabled by pushing position 1
switch to the “on” position. After confi guration the switch must be moved
to the “off” position.