Sterlco GP Series 5-15 HP Portable Chillers User Manual

Page 50

Advertising
background image

GP Series Portable Chillers

Chapter 4: Operation

50 of 93

Variable

Description

Access Level

Operator

Supervisor

Analog Out 3

Determines how analog output 3 is used. It can be
set to CHIL IN (retransmission of the chiller in
temperature), CHIL OUT (retransmission of the
chiller out temperature), FROM PROC
(retransmission of the from process temperature) or
TO PROC (retransmission of the to process
temperature).

x

Analog Out 4

Determines how analog output 4 is used. It can be
set to CHIL IN (retransmission of the chiller in
temperature), CHIL OUT (retransmission of the
chiller out temperature), FROM PROC
(retransmission of the from process temperature) or
TO PROC (retransmission of the to process
temperature).

x

Digital In 8

Determines how digital input 8 is used. It can be set
to START/STOP (remote start stop), NO
WARNING (normally open warning alarm), NC
WARNING (normally closed warning alarm), NO
FAULT (normally open fault alarm), NC Fault
(normally closed fault), PHASE MNTR (power
phase monitor), TMP SAFETY (high temp safety)

x

Start Mode

When Digital In 8 is configured to START/STOP
this determines if the chiller’s online status is
determined by the button on the display (LOCAL) or
digital input 8 (REMOTE).

x

Chil Cntl Sens

Determines which sensor is used to control the
chiller. It can be set to CHIL OUT (chiller out
temperature), CHIL IN (chiller in temperature), TO
PROC (to process temperature) or FRM PROC
(from process temperature).

x

Proc Cntl Sens

Determines which sensor is used to control the
process loop. It can be set to TO PROC (to process
temperature) or FRM PROC (from process
temperature).

x

Pump 2 OL Alm

When set to CRIT, the pump 2 overload alarm will
deactivate compressors and pumps. When set to
WARN, compressors and pumps are allowed to
continue to run when the pump 2 overload alarm
occurs.

x

Flow 2 Alm Type

When set to CRIT, the flow 2 alarm will deactivate
compressors and pumps. When set to WARN,
compressors and pumps are allowed to continue to
run when the flow 2 alarm occurs.

x

Alarm Out

Determines when the alarm output is activated.
When set to ALL ALARMS, the output is activated
when any new alarm occurs. When set to CRIT
ALARMS, the output will only activate when
critical alarms (those that force the pump or
compressor off) occur.

x

Network Prot

Determines what network protocol is used for
communications. This can be set to BACNET485,
BACNET IP, MODBUS485, MODBUS IP, LON or
WEB.

x

Network Baudrate

Determines the baudrate for communications.

x

Network Address

Determines the network address of the chiller on the
network.

x

Units

Determines if STANDARD (English) or METRIC
units are used.

x