GP Series Portable Chillers

Chapter 7: Appendix

81 of 93


Notes:
• Customer use of ductwork requires the high pressure fan option.
• Allow 30 in. (77 cm) minimum clearance around the chiller footprint to facilitate free passage of

cooling air and service accessibility.

• Figure 20 shows the pressure loss per foot of ductwork. Calculate the total equivalent length before

using the data below.

• Support ductwork from the building structure, not off of the chiller.
• Back draft damper to outside must be closed at all times when fan/blower is not operating. Size the

damper so that the pressure drop across is no greater than 0.2 in WG (50 Pascal) at the rated output.

• Chillers are designed to operate at a condensing entering air temperature of 60ºF (16ºC) minimum

without optional Variable Frequency Drive.

Figure 20 - Loss of Pressure through round duct - inches of water column per equivalent foot

60 hz Condenser Fan Flow Rate (cfm / cmm)

50 hz Condenser Fan Flow Rate (cfm / cmm)

Nominal
Duct
Diameter
(in / cm)

GPAC-20

GPAC-30 GPAC-40 GPAC-50 GPAC-20 GPAC-30 GPAC-40 GPAC-50

4230 / 120

6343 /

180

8458 /

240

12687 /

360

3525 /

100

5286 /

150

7048 /

200

10573 /

300

18 / 45

0.003

0.007

0.013

0.03

0.002

0.005

0.009

0.020

20 / 50

0.002

0.005

0.008

0.02

0.001

0.003

0.005

0.012

22 / 55

0.001

0.003

0.005

0.01

0.002

0.003

0.007

24 / 60

0.002

0.003

0.007

0.001

0.002

0.005

26 / 65

0.001

0.002

0.004

0.001

0.003

28 / 70

0.001

0.003

0.002

30 / 75

0.002

0.002

32 / 80

0.002

0.001

36 / 90

0.001

Note: 1 inch of water column = 250 Pascal