Changing UV Bulb

TR

10

TR

15

TR

20

Turn off chiller and unplug the chiller, Remove the housing

1

(see directions on p.19)

Unscrew the ring nut for the UV sterilizer port.

2

Remove rubber stopper from the quartz sleeve

3

Unplug the old UV lamp from the 4-pin socket., remove and discard lamp.

4

Slide new UV lamp into quartz sleeve, plug into 4-pin socket, return rubber stopper into sleeve

5

Do not touch the glass of the UV bulb with your bare hands.

Tighten ring nut over quartz sleeve

6

Replace housing and air filter. Replace ring nuts and valves.

7

Open shut off valves, restart pump and check for leaks. Turn UV on by pressing UV button.

8

Hold down UV button for 10 seconds to reset AL2 code.

9

It is time to replace the UV Lamp
when the AL2 code flashes on the
control panel

Changing the Fuse

Changing the Fuse

Turn off and unplug the chiller before changing the fuse.

1

Remove the fuse holder from socket using a flathead screwdriver.

2

Remove blown fuse from clip and discard.

3

Push out the spare fuse (contained in the fuse holder), place new fuse in the clip, replace fuse holder.

4

Turn off chiller and unplug the chiller, Remove the housing

1

(see directions on previous page)

Remove the blue plastic cover from fuse, remove old fuse from clips

2

Install new fuse, replace blue plastic cover, replace chiller housing.

3

Spare Fuse

Note: Some wires were removed for these photos

Fuse Clip

Fuse Holder

TR

5

TR

10

TR

15

TR

20

TR

30

TR

60

Do not touch the glass of the UV bulb with your bare hands.
Oils on your hands will dramatically decrease the lifespan of the UV lamp. Use a clean
cloth to handle the lamp during installation.

WARNING: