Please disconnect power completely and read the
entire instruction manual carefully before installation.

3.1 Select the required location
3.1.1 Sensor adjustment
Fig. 2 shows the way coverage alters with ceiling height and with
adjustments of the METER dial setting.

Ceiling Height (H)

Detection Coverage Diameter (D)

with METER on +

2m 7m

2.5m

7m

3m

10m

3.5m

12m

4m

12m

4.5m

12m

If the METER control is turned to – the coverage diameter is
substantially reduced.
We do not recommend the use of these units with ceiling heights
greater than 4.5m.
3.1.2 Helpful tips for installation
As the sensor responds to temperature change or moving heat sources,
please avoid the following conditions:
• Avoid highly reflective surfaces within the detection range.
• Avoid movable objects e.g. curtains and plants in the detection range
(these may cause erroneous detections when moved by air flow from
fans or air conditioner).
• Avoid heat sources (e.g. heating vents, radiators, air conditioners and
filament lamps) in detection range.
• Avoid fans drawing air across the sensor lens.

1

Package Contents

2

Product Description

3

Installation and Wiring

Technical Specifications

Rated Voltage:

230V ~ ±10% 50Hz

Loads:

PDSM362 (2 channels):

Load I ( L ) for Lighting: µ (contact

separation)

Incandescent lamp: max. 2000W

Mains halogen lamp: max. 1000W

LV halogen lamp: max. 600VA

Fluorescent lamp: max. 900VA/100µF

LED lamp: max 400W

Load II (D1-D2) for HVAC:

Max. 5A (cosØ =1) 250VAC or 30VDC

Max: 1/10HP (73W)

PDSM361 (1 channel):

Load I ( L ) for Lighting: µ (contact

separation)

Incandescent lamp: max. 2000W

Mains halogen lamp: max. 1000W

LV halogen lamp: max. 600VA

Fluorescent lamp: max. 900VA/100µF

LED lamp: max 400W

Timer Adjustment

PDSM362:

(constant adjustment):

TIME1 (for lighting):

Adjustable from 5 sec. to 20 min.

(continuously adjustable)

TIME2 (for HVAC):

Adjustable from 10 sec. to 60 min.

(continuously adjustable)

PDSM361:

TIME: Adjustable from 5 sec. to 20 min.

(continuously adjustable)

LUX (light level)

Adjustable from 10 LUX to 2000 LUX

Adjustment:

(continuously adjustable)

Max. Detection Coverage: 360º cone shape from ceiling height of

2.5m giving 7m dia. coverage at floor

level (for affect of ceiling height on

coverage see section 3.1.1)

Conforms To

EC Directives

All procedures indicated in this manual must be
carried out by a professional installer.

METER Adjustment:

Adjustable continuously from

+ giving maximum detection

coverage at floor level to – giving a

substantially reduced detection

coverage at floor level

Operating Temperature:

0ºC to +45ºC

Environmental Protection: Class II, IP40

Fig. 2

Fig. 3

Fig. 6

Fig. 1

Side View

Top View (showing individual

beam pattern at floor level)

Fig. 8

Fig. 7

Surface Mount

Presence Detector

PDSM362/PDSM361

Instructions

2.1 Features
The PDSM362/PDSM361 controller is a ceiling surface mount
presence detector for indoor applications in commercial and
domestic locations. PDSM361 covers lighting applications only,
whereas PDSM362 can control lighting and HVAC
(heating, ventilating and air conditioning) applications.
Adjustment of Time and LUX values can be made either by the dial
controls on the sensor body or by the IR10 Infrared remote control.
• PDSM362 has two relays for outputs load I and load II:
load I is for lighting control and load II has voltage free contacts
for HVAC control which operate at all LUX (light) levels.
• The sensor has a very high density of sensitive beams covering the
detection area. These are evenly distributed ensuring no dead spots
and detection of the smallest movements.
• Either side or bottom cable entry.
• Built-in red LED in sensor giving confirmation of remote control
settings and easy test operation.

2.2 Dimensions (see Fig. 1)

Models PDSM362/PDSM361

3.3 Installation procedure
3.3.1 Insert large flat blade screwdriver into the groove as shown
each side in turn and twist (see Fig. 6) to remove outer cover.
3.3.2 To separate bottom case from lens body force a small flat blade
screwdriver into the hidden gap shown partially exposed in Fig. 7 then
push screwdriver in towards centre and lever bottom case assembly
away from lens body pins.
3.3.3 Remove cardboard and screws used to assemble and fix
the sensor (see Fig. 8).

3.2 Wiring
3.2.1 Lighting and HVAC are controlled by one PDSM362 (see Fig. 3).

Fig. 4

Fig. 5

3.2.2 Lighting is controlled by two PDSM362’s to enlarge
detection range (see Fig. 4).

3.2.3 Lighting is controlled by a PDSM361 (see Fig. 5).

PDSM362 – 6A breaker
A circuit breaker (250VAC,6A) type C according to EN60898-1
of load shall be installed in the fixed wiring for protection of load II.
PDSM361, PDSM362 – 10A breaker
A circuit breaker (250VAC,10A) type C according to EN60898-1
of load shall be installed in the fixed wiring for protection of load I.

This product must be
protected by a fuse or
circuit breaker with a
maximum rating of
10A or lower.