3 year guarantee – Timeguard PDSM362 User Manual

Page 2

Advertising
background image

PDSM362/PDSM361 can also be controlled by the infrared remote
controller IR10. As well as allowing remote setting of times and
light level the IR10 also enables continuous operation for 8 hours
in ON or OFF modes as well as continuously in detection mode
controlled by or independent of light level.
The IR10 is invaluable during commissioning enabling changes to
be made without resorting to ladders.
Further to this the IR10 can download stored settings from one
sensor to additional sensors in the same area.

4.1.1 TIME control adjustment
These are delay times between the sensor being triggered and the
controller switching off assuming no further detections are made.
If there are additional detections the time delay applies from
the latest detection.

PDSM362:
TIME 1: Adjustable from 5 sec. to 20 min. (lighting). (Extendable to
30 min. and 60 min. when in use with the IR10 remote controller).
TIME 2: Adjustable from 10 sec. to 60 min. (HVAC).

PDSM361:
TIME: Adjustable from 5 sec. to 20 min. (lighting). (Extendable to
30 min. and 60 min. when in use with the IR10 remote controller).
4.1.2 LUX control adjustment
The LUX level below which the sensor will operate is adjustable
from 10 LUX (operation only after dusk) to 2000 LUX (operation at
any light level).

4.1.3 METER control adjustment
This control sets the diameter of detection coverage at floor level.
Assuming a ceiling height of 2.5m at the + end of the scale the
coverage diameter will be 7m, at the – end of the scale the coverage
diameter will be 1m.
The effect of METER control at other ceiling heights is shown in
section 3.1.

4.2 Test Mode
4.2.1 Sensor warm up
The detector will take a minimum of 60 seconds to warm up when the
power is connected to it for the first time or if the power is being
re-connected after being turned off.
During this period load I and the sensor LED will both be on. After the
warm up is finished the sensor will revert to operation according to
the settings of the controls on the sensor body.
4.2.2 LED function
There is a red LED (see Fig. 12) built into the sensor and visible through
the PIR lens that shows the status of the loads and enables testing to
be carried out without the loads being connected.
If the IR10 remote controller is in use the LED will flash to give
confirmation of the commands and adjustments made by the IR10.

Fig. 9-A (Bottom entry)

Fig. 9-B (Side entry)

Fig. 10

4

Test and Operation

5

Troubleshooting

6

Optional Remote Control – IR10

4.1 Time, LUX and Meter Controls
Following marked values (excepting TEST and

) are approximate,

the values are continuously adjustable over the control range
(see Fig. 11-A & Fig. 11-B).

Fig. 11-A (PDSM362 control dials)

Fig. 11-B (PDSM361 control dials)

When the PDSM362/PDSM361 is not working as expected go
through the troubleshooting guide below.

Fig. 12

Problem

Possible

Suggested

Cause

Solution

Lights do not
turn on.

Lighting or
HVAC does not
turn off.

LED does not
turn on.

Nuisance
triggering.

1. Power is not turned on.
2. Incorrect control

dial setting.

3. Incorrect wiring.

4. Faulty load.

1. Incorrect time setting.

2. Incorrect wiring.

1. Out of detection range.

2. Power supply not on.
3 ‘TIME’ knob setting

isn’t on ‘Test’.

4. Incorrect wiring.

There are heat sources,
HVAC vents/fans, highly
reflective surfaces or
anything which may be
swayed by air movement
within the detection
coverage.

1. Switch on the power.
2. Check if control dials are

set to the correct position,
then supply the power to
check if the LED will turn on.

3. Refer to wiring diagrams

(Fig. 3 to Fig. 6)

4. Replace the faulty load.

1. Check that the correct delay

time is set on either TIME 1
or TIME 2 control dial.
Then determine if nuisance
triggering is keeping the
unit turned on.

2. Make sure supply and load

wires are connected correctly.

1. Walk within the effective

detection range.

2. Switch the power on.
3. Turn the control dial

to ‘Test’.

4. Refer to wiring diagrams

(Fig. 3 to Fig. 5).

Avoid aiming the toward
any heat sources, such as
air conditioners, electric
fans, heaters or any highly
reflective surfaces.
Make sure there are no
swaying objects within the
detection coverage.

3 Year Guarantee

In the unlikely event of this product becoming faulty due to

defective material or manufacture within 3 years of the date
of purchase, please return it to your supplier in the first year

with proof of purchase and it will be replaced free of charge.

For years 2 and 3 or any difficulty in the first year telephone

the helpline on

020 8450 0515.

Helpline

020-8450-0515

or email [email protected]

For a product brochure please contact:

Timeguard Ltd.

020-8452-1112

or email [email protected]

A

Group company

67-058-276 (iss. 4)

For assistance with the product please contact:

Fig. 13

3.3.4 There are two methods of cable entry into the unit. One feeds
into the bottom case (Fig. 9-A), another feeds into the side of the
bottom case and outer cover (Fig. 9-B). Select your preferred cable
entry and score round the appropriate knock-out pattern in the bottom
case with a sharp knife. If side entry is chosen the knock-out pattern
in the outer cover will need to be scored as well. Push out the chosen
knock-outs and feed the wires through, then connect the wires to the
corresponding terminal blocks.

3.3.5 Insert the lens body pins into the bottom case contacts,
fasten it with screws firmly and snap on the outer cover (see Fig. 8).
3.3.6 Recheck and wipe slightly with a clean dry cloth if the sensor
surface is dirty.
3.3.7 There is a pattern of slots on the bottom case that should enable
the fixing holes of the previous unit to be used. Fasten bottom case
onto the ceiling with wood screws (see Fig. 10).

3.3.8 Restore the power.

4.2.3 Walk test
Turn supply on and wait at least 60 seconds for the system to
settle down.
Turn Time 1 control to the Test position. This means that the sensor
LED and load I will turn on for 2 seconds after triggering and then
be off for 3 seconds after which the sensor can be re-triggered.
The triggering is independent of light level.
The installer should move around in the detection area to establish
that it is all covered. If necessary the METER control dial should be
adjusted, after which the area should be walk tested again to
confirm coverage is as required.
To confirm that load 2 (HVAC) is operating correctly for a PDSM362,
carry out the following:-
Turn LUX (light level) to its minimum value (10 LUX) to stop load 1
(lights) from turning on. Then turn Time 2 (HVAC) to minimum value
(10s) and carry out a limited walk test to confirm correct operation
of load 2.

Advertising
This manual is related to the following products: