4.2 Examples of communications to be written

Example: Request message: This requests this product set at address 03 to set "the A1F setting to
(High-level computer)

135" (write 135).

(Set the event 1 function to the following: Error alarm type to be PV
error alarm 1, alarm type to be deviation lower limit alarm 3 and
additional function to be alarm hold + standby sequence (5).)

In response to that,

Response message: This returns a notice that the request message has been received.
(This product)

*Check that it has been written by reading the data separately.

Write request message (transmitted from a high-level computer)

Code

Code, data

ASCII code, note 2)

① Start code

STX

02H

② Address

03

32H 33H

③ Request contents

W (Write)

57H

④ Identifier, note 1)

A2F

41H 33H 46H

⑤ Numerical data

00135

30H 30H 31H 33H 35H

⑥ End code

ETX

03H

⑦ BCC data request

56H

response

04H

⑧ Acknowledge code

ACK

06H


Note 1): See "7. Table of identifiers (codes)."
Note 2): For the ASCII codes, see "8. Table of ASCII codes."

Response message (returned from this product)