What results are generally acceptable – UEi Test Instruments C20KIT User Manual

Page 8

Advertising
background image

6

a

tmoSpheriC

g

aS

f

ired

b

urNerS

CO2 ................................................................................... 7.0 to 8.0% CO2

Stack Temperature ......................................................... 325 to 500°F

Draft (Water Column Inches) .......................................... -.02 to -.04wc”

Carbon Monoxide (parts per million) ............................ <100ppm

g

aS

f

ired

p

ower

b

urNerS

CO2 ................................................................................... 6.0 to 7.0% CO2

Stack Temperature ......................................................... 275 to 500°F

Stack Draft (Water Column Inches) ............................... -.02 to -.04wc”

Overfire Draft (Water Column Inches) .......................... -.02wc”

Carbon Monoxide (parts per million) ............................ <100ppm

o

il

f

ired

b

urNerS

(#2 o

il

f

uel

)

CO2 ................................................................................... 6.6 to 8.0% CO2

Stack Temperature ......................................................... 325 to 600°F

Stack Draft (Water Column Inches) ............................... -.04 to -.06wc”

Overfire Draft (Water Column Inches) .......................... -.02wc”

Carbon Monoxide (parts per million) ............................ <100ppm

Smoke .............................................................................. 0

(or manufacturer’s recommendation)

p

oSitive

o

verfire

g

aS

& o

il

CO2 ................................................................................... 5.8 to 10.3% CO2

Stack Draft (Water Column Inches) ............................... -.02 to -.04wc”

Overfire Draft (Water Column Inches) .......................... +0.4 to +0.6wc”

Carbon Monoxide (parts per million) ............................ <100ppm

NOTE: Follow manufacture guidelines for the specific equipment being serviced.

- Temperature and draft targets are included for reference only.

The C20 does not measure these parameters

WHAT RESULTS ARE GENERALLY ACCEPTABLE