Roubleshooting, Hart – Amana Gas Furnance S)8 User Manual

Page 38

Advertising
background image

38

T

ROUBLESHOOTING

C

HART

Associated

LED Code

2

2

LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.

4

4 FLASHES

• Circulator blower runs

continuously. No furnace
operation.

• Integrated control module

diagnostic LED is flashing

FOUR (4) flashes.

6

6 FLASHES

7

7 FLASHES

• Furnace fails to operate.

• Integrated control module

diagnostic LED is flashing
SIX (6) flashes.

• No furnace operation.

• Normal furnace

operation.

• Integrated control module

diagnostic LED is
flashing SEVEN (7)
flashes.

• Rollout limit open.

• Integrated control

module fuse is
blown.

• Flame sense

microamp signal is
low.

• Flame sensor is coated/

oxidized.

• Flame sensor incorrectly

positioned in burner
flame.

• Lazy burner flame due to

improper gas pressure or
combustion air.

• Sand flame sensor.

• Inspect for proper sensor

alignment.

• Compare current gas

pressure to rating plate
info. Adjust as needed.

• Turn power OFF

prior to repair.

• Clean flame sensor

with steel wool.

• See “Vent/Flue

Pipe” section for

piping details.

• See rating plate for

proper gas

pressure.

• See “Vent/Flue Pipe”

section for piping
details.

• Replace induced

draft blower with
proper replacement
part.

• Replace integrated

control module fuse
with 3A automotive
fuse.

• Read precautions in

“Electrostatic
Discharge” section
of manual.

• Replace rollout limit

with correct
replacement part.

• Primary limit

circuit is open.

• Check burners for proper

alignment.

• Check flue and air inlet

piping for blockage,

proper length, elbows,

and termination. Correct

as necessary.

• Check rollout limit. Replace

if necessary.

• Check induced draft

blower for proper

performance. Replace, if

necessary.

• Tighten or correct wiring

connection.

• Repair short in 24 volt AC

control/safety circuit(s).

• Replace integrated control

module fuse (3A).

• Flame rollout.

• Misaligned burners,

blocked flue and/or air
inlet pipe, or failed
induced draft blower.

• Loose or improperly

connected wiring.

• Short in 24 volt AC

control circuits or safety
circuits.

• Faulty rollout limit.

• Induced draft blower and

circulator blower runs

continuously. No furnace

operation.

• Integrated control module

diagnostic LED is flashing

FIVE (5) flashes.

5

5 FLASHES

• Flame sensed

with no call for
heat.

• Short to ground in flame

sense circuit.

• Correct short at flame

sensor or in flame
sensor wiring.

• Turn power OFF

prior to repair.

• Insufficient conditioned air

over the heat exchanger.
Blocked filters, restrictive
ductwork, improper
circulator blower speed, or
failed circulator blower.

• Faulty primary limit switch.

• Loose or improperly

connected wiring.

• Check primary limit.

Replace if necessary.

• Check filters and

ductwork for blockage.
Clean filters or remove
obstruction.

• Check circulator blower

speed and performance.
Correct speed or replace
blower if necessary.

• Tighten or correct wiring

connection.

• Turn power OFF

prior to repair.

• Replace primary

switch with proper
replacement part.

• Replace blower

with correct
replacement part.

Cautions

& Notes

Corrective Action

Possible Causes

Fault

Description(s)

Symptoms of

Abnormal Operation

Associated

LED Code