In the HMU/HLU configuration, for example, for detailed information about the different types of alarms, refer to the
“Managing Alarms” section in the

HMU-319, H2TU-C-319, or H4TU-C-319 User Manuals

. Specifically, the manual

describes the types of alarms the HMU-319 reports, when the alarm occurs, and how to respond to the alarm using
the ACO.

Table 1-2. Alarms Wire-wrap Field Functional Description

Alarm

Alarm Description

Function

CRIT AUD

Critical Audible

There is a critical alarm active on the HMS-318
List 3 shelf. Connect this relay to the critical
alarm audible indicator of the CO alarm
system.

CRIT VIS

Critical Visible

There is a critical alarm active on the HMS-318
List 3 shelf. Connect this relay to the critical
alarm visual indicator of the CO alarm system.

MAJ AUD

Major Audible

There is a major alarm active on the HMS-318
List 3 shelf. Connect this relay to the major
alarm audible indicator of the CO alarm
system.

MAJ VIS

Major Visible

There is a major alarm active on the HMS-318
List 3 shelf. Connect this relay to the major
alarm visual indicator of the CO alarm system.

MIN AUD

Minor Audible

There is a minor alarm active on the HMS-318
List 3 shelf. Connect this relay to the minor
alarm audible indicator of the CO alarm
system.

MIN VIS

Minor Visible

There is a minor alarm active on the HMS-318
List 3 shelf. Connect this relay to the minor
alarm visual indicator of the CO alarm system.

SYS ID

System ID

There is a critical, major, or minor alarm active
on the HMS-318 List 3 shelf. Connect this relay
to the equipment rack alarm indicator.

ACO

Alarm Cutoff

External Alarm Cutoff (ACO) function silences
active audible alarms (see

“Alarm Cutoff

(ACO)” on page 1-6

).

GND

Ground

External ground

EXT TEMP

External Temperature
Thermostat

Thermal control (digital temperature sensor).
Connect this pin to an external snap-action
thermostat to activate the fan relay. This
thermostat provides a switch closure to ground
that is sensed by the HMU-319.

NO COM FAN

Fan Control

The Fan Control manually disables a Fan
Assembly using the NO and COM fan control
contacts.