Issue 1031

Table 8

Details of Intake and Exhaust Piping Terminations for
Direct Vent Installations

NOTE: In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged to outdoors.

Intake and exhaust pipes may be routed either horizontally
through an outside wall or vertically through the roof. In
attic or closet installations, vertical termination through the
roof is preferred. Figures 26 through 37 show typical
terminations.

1.

Exhaust and intake exits must be in same pressure zone.
Do not exit one through the roof and one on the side.
Also, do not exit the intake on one side and the exhaust
on another side of the house or structure.

2.

Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to
illustrations). Maximum separation is 3" (76 mm) on
roof terminations and 6" (152 mm) on side wall
terminations.

3.

On roof terminations, the intake piping should terminate
straight down using two 90° elbows (See Figure 26).

4.

Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust piping
at the point where it exits the structure to improve the
velocity of exhaust away from the intake piping. See
Table 8.

5.

On field supplied terminations for side wall exit, exhaust
piping may extend a maximum of 12 inches (305 mm)
for 2" PVC and 20 inches (508 mm) for 3" (76 mm) PVC
beyond the outside wall. Intake piping should be as
short as possible. See Figures 28 and 29.

NOTE: Care must be taken to avoid recirculation of exhaust
back into intake pipe.

6.

On field supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of the
intake pipe without a termination elbow is 8" and a
minimum distance of 6" with a termination elbow. See
Figures 28 and 29.

7.

If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other
ob-structions, piping must be supported every 24" (610
mm) as shown in Figures 28 and 29. See Figure 32.
When exhaust and intake piping must be run up an
outside wall, the exhaust piping must be terminated with
pipe sized per Table 8. The intake piping may be
equipped with a 90° elbow turndown. Using turndown
will add 5 feet (1.5 m) to the equivalent length of the
pipe.

8.

Based on the recommendation of the manufacturer, a
multiple furnace installation may use a group of up to
four terminations assembled together horizontally, as
shown in Figure 32.

Figure 27

DIRECT VENT FLUSH MOUNT TERMINATION KIT

(51w11)

DIRECT VENT ROOF TERMINATION KIT

(15F75 OR 44J41)

Figure 26

EXHAUST PIPE TERMINATION SIZE REDUCTION