APPENDIX A: ALLOWABLE AMPACITIES OF INSULATED CONDUCTORS

This appendix provides guidelines for selecting AWG wire size based on the temperature rating
of the conductor and the anticipated load. The information contained is from Table 310-16 of
the National Electrical Code document, ANSI/NPFA 70 (1978).

Note: Information for aluminum conductors has been omitted from the table here
because copper conductors only are recommended for use with the ADC panel.

Table 310-16 (NEC): Allowable Ampacities of Insulated Conductors, Rated O Through 2000 Volts, 60

° to

90

°C (140° to 194°F), Not More Than Three Current-Carrying Conductors in Raceway or Cable or Earth

(Directly Buried), Based on Ambient Temperature of 30

°C (86°F)

SIZE

TEMPERATURE RATING OF CONDUCTOR

AWG

KCMIL

60

°C

(114

°F)

60

°C

(114

°F)

60

°C

(114

°F)

TYPES

TW*,

UF*

TYPES

FEPW*,

RH*, RHW*,

THHW*,

THW*,

THWN*,
XHHW*,

USE*, ZW*

TYPES

TBS, SA,

SIS, FEP*,

FEPB*, MI,

RHH*, RHW-2,

THHN*,

THHW*, THW-2*,

THWN-2*,

USE-2,

XHH,

XHHW*

XHHW-2

ZW-2

18

....

....

14

16

....

....

18

14

20*

20*

25*

12

25*

25*

30*

10

30

35*

40*

8

40

50

55

6

55

65

75

4

70

85

95

3

85

100

110

2

95

115

130

1

110

130

150

1/0

125

150

170

2/0

145

175

195

3/0

165

200

225

4/0

195

230

260

250

215

255

290

300

240

285

320

350

260

310

350

400

280

335

380